Planning
5.1
Overview of planning
Robot controller
5.2
Electromagnetic compatibility (EMC)
Description
If connecting cables (e.g. DeviceNet, etc.) are routed to the control PC from
outside, only shielded cables with an adequate degree of shielding may be
used. The cable shield must be connected with maximum surface area to the
PE rail in the cabinet using shield terminals (screw-type, no clamps).
This is an overview of the most important planning specifications. The pre-
cise planning depends on the application, the robot type, the technology
packages used and other customer-specific circumstances.
For this reason, the overview does not claim to be comprehensive.
Step
Description
Information
1
Electromagnetic compatibility (EMC)
(
>>>
2
Installation conditions for robot controller
(
>>>
page 66)
3
Connection conditions
(
>>>
page 67)
4
Power supply connection
(
>>>
5
E-STOP circuit and safeguard
(
>>>
6
Configuration of interface X11
(
>>>
7
Equipotential bonding
(
>>>
8
KCP coupler (optional)
(
>>>
pler option" page 75)