COMMON RAIL SYSTEM
V3800-CR-TE4,V3800-CR-TIE4, DM
1-S153
(9) Intake Air Temperature Error (DTC P0112 / 172-4, P0113 / 172-3)
P0112 / 172-4: Intake air temperature error (Low side)
Behaviour during malfunction:
• Amount of white smoke increases at low temperatures
Detection item:
• Ground short circuit of sensor / harness
DTC set preconditions:
• Battery voltage is normal
DTC set parameter:
• Voltage of intake air temperature sensor is 0.05 V or less
Engine warning light:
• ON
System action:
• At start-up =
−
20 °C (
−
4 °F) [default value]
• Under other conditions = 40 °C (104 °F) [Default value]
Recovery from error:
• Diagnostic counter = zero
9Y1200192CRS0680US0
P0113 / 172-3: Intake air temperature error (High side)
Behaviour during malfunction:
• Amount of white smoke increases at low temperatures
Detection item:
• Open circuit or +B short circuit of sensor / harness
DTC set preconditions:
• Battery voltage is normal
DTC set parameter:
• Voltage of intake air temperature sensor is 4.9 V or above
Engine warning light:
• ON
System action:
• At start-up =
−
20 °C (
−
4 °F) [default value]
• Under other conditions = 40 °C (104 °F) [Default value]
Recovery from error:
• Diagnostic counter = zero