1.6 Supported standards and functions

8.M36X1.XX3X.3X12 / 8.M3661R.XX3X.3X12 / 8.M5861.XXXX.XX12:  

 

 

  

Output: 4 … 20mA 

   Resolution: 

12 

bits 

 

 

 

Max. measuring range: 65536 revolutions

 

 

 

Min. measuring range: 22.5°

 

 

 

Zero point display: 0 … 1°

8.M36X1.XX4X.4X12 / 8.M3661R.XX4X.4X12 / 8.M5861.XXXX.XX12:

 

 

  

Output: 0 … 10 VDC 

   Resolution: 

12 

Bit 

 

 

 

Max. measuring range: 65536 revolutions

 

 

 

Min. measuring range: 22,5°

 

 

 

Zero point display: 0 … 1°

8.M36X1.XX4X.5X12 / 8.M3661R.XX4X.5X12 / 8.M5861.XXXX.XX12: 

 

 

  

Output: 0 … 5 VDC 

   Resolution: 

11 

bits 

 

 

 

Max. measuring range: 65536 revolutions

 

 

 

Min. measuring range: 22.5°

 

 

 

Zero point display: 0 … 1°

1.7 Optional functions

• Measuring range scaling via scaling inputs (max. 10,000 cycles)

• Limit switch function

• Direction of rotation: CCW (is factory-set and cannot be modified by the user.)

Содержание Sendix M3661

Страница 1: ...R60722 0002 Index 3 Analog U I Manual Absolute multiturn encoder Sendix M3661 M3681 Order code 8 M36X1 XXXX XX12 Sendix M3661R Order code 8 M3661R XXXX XX12 Sendix M5861 Order code 8 M5861 XXXX XX12...

Страница 2: ...0 Fax 49 0 7720 21564 servicecenter kuebler com Document no R60722 0002 Index 3 Document name Manual analog U I Sendix M3661 M3681 order code 8 M36X1 XXXX XX12 Sendix M3661R order code 8 M36X1R XXXX X...

Страница 3: ...ardware characteristics 4 1 6 Supported standards and functions 5 1 7 Optional functions 5 2 Electrical installation 6 2 1 Electrical installation 6 2 2 Terminal assignment 6 3 Function and status LED...

Страница 4: ...10V 15 30 VDC max 30 0 mA 0 5V 10 30 VDC max 30 0 mA 1 4 Load at the output max output current Output 4 20mA at 10 VDC max 200 Ohm at 24 VDC max 900 Ohm at 30 VDC max 1200 Ohm 0 10V 0 5V min 1kOhm loa...

Страница 5: ...X 4X12 8 M3661R XX4X 4X12 8 M5861 XXXX XX12 Output 0 10 VDC Resolution 12 Bit Max measuring range 65536 revolutions Min measuring range 22 5 Zero point display 0 1 8 M36X1 XX4X 5X12 8 M3661R XX4X 5X12...

Страница 6: ...ndividually before commissioning 3 current 1 2 A B Signal 0 V V I SET 11 Set 21 Cable color WH BN GN GY PK Interface Connection type M12 connector 5 pole 3 current 3 4 Signal 0 V V I SET 11 Set 21 Pin...

Страница 7: ...upply and the wiring Green LED flashes in 250 ms cycles Service mode Encoder in Service mode Please contact the service department of the manufacturer Green LED constantly on Encoder in operation Red...

Страница 8: ...r measu ring range Green red green sequence 1x 1x 1x Reset of the scaled measuring range Default measuring range is loaded Preset is performed at the current position 4 Standard function As a standard...

Страница 9: ...desired measuring range To trigger the scaling operation the corresponding scaling input must be connected with the supply voltage V for at least 1 second Scaling process 1 Turn the shaft to the desi...

Страница 10: ...ing 4 3 Resetting the scaled output signal 1 Connect scaling inputs 1 2 with V for at least 1 second 2 The LED sequence green red green is displayed The factory set scaling of the output signal is ava...

Страница 11: ...switch function 5 Abbreviations used CW Direction of rotation clockwise looking at the shaft CCW Direction of rotation counterclockwise looking at the shaft MT Revolution counter ST Angle information...

Страница 12: ...www kuebler com K bler Group Fritz K bler GmbH Schubertstrasse 47 D 78054 Villingen Schwenningen Germany Phone 49 7720 3903 0 Fax 49 7720 21564 info kuebler com www kuebler com R60722 0002 Index 3...

Отзывы: