Quick Installation OMNI960 Series Digital Video Recorders
Revised October, 2014 10
Peripheral Connections
Wiring of Alarm Input (OMNI960-32 only).
The alarm input is an open/closed relay. To connect the alarm input to the device, use the following diagram.
Note:
If the alarm input is not an open/close relay, please connect an external relay between the alarm input and the device.
Wiring of Alarm Output
To connect to an alarm output (AC or DC load), use the following diagram:
DC Load Connection Diagram AC Load Connection Diagram
For DC low current load, the jumpers can be used within the limit of 12V/1A safely.
To connect an AC load or DC high current load, jumpers should be left open (you must remove the jumper on the motherboard in the NVR). Use an
external relay for safety (as shown in the figure above).
There are 4 jumpers (JP1, JP2, JP3, and JP4) on the motherboard, each corresponding with one alarm output. By default, jumpers are connected. To
connect an AC load, jumpers should be removed.
Example:
If you connect an AC load to the alarm output 3 of the DVR, then you must remove the JP 3.
Alarm Connection
To connect alarm devices to the DVR:
1.
Disconnect
pluggable block
from the ALARM IN /ALARM OUT terminal block.
2.
Press and hold the orange part of the
pluggable block
; insert signal cables into slots and release the orange part. Ensure signal cables are in tight.
Connect
pluggable block
back into terminal block
Note:
Alarm input/output connections are valid for the OMNI960-32
models only.