System variants

System variant 1: Solar thermal system

The program controls the solar circuit pump depending 
on   the   temperature   of   the   solar   collector   and   the 
storage   tank   temperature.   If   the   temperature   in   the 
solar collector is higher than the buffer temperature, 
the solar circuit pump is turned on. The solar pump 
remains running for a minimum running time and is 
earliest turned on after a minimum idle time.
The buffer is charged until the maximum storage tank 
temperature is reached or the start-up criteria is not 
met any more.

CF1 Sensor 1
SF1 Sensor 2

Overheating protection

In solar thermal systems it comes to the overheating of the solar fluid if the energy from the 
collectors can be led away not enough. In this stagnation case the medium can evaporate. In 
this  case typically used solar  pumps  cannot build up enough pressure to  lift the liquid 
medium up to the highest system point (collector escape). In this working condition the pump 
is considerably loaded, no solar energy is won to the use and electric energy is used for the 
pump. 
In the stagnation case the solar pump CP1 is  switched OFF  at a collector temperature of 
130 °C with a hysteresis by 20 K.

Actual pump 
running/idle time

The solar pump CP1 is switched on by presentation of the thermal switch condition described 
on top on at least 1 minute. The solar pump remains switched off for at least 3 minutes if the 
thermal switch condition is not given any more.

Collector minimum 
temperature

At low collector temperatures there sinks the efficiency of the solar thermal system, because 
the energy consumption of the solar pump is unfavorably high in proportion to the solar 
energy yield. The solar pump CP1 is only switched on if the collector temperature at least 20  
°C amounts.

Collector Anti-freeze

The collector pump is turned on if the temperature at the collector sensor drops below 5 °C. 
At   6 °C   it   is   turned   off   again,   but   only   after   the   minimum   running   time   set   elapsed.
This customized function is not available in standard devices.

Status indication using Power-LED

● ON  ○ OFF

Display

Device powered-on

2 seconds OFF    ● ● ● ● ● ● ● ● ● ● ● ● ● ● 

Function without additional information 

● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● 

Sensor break of Sensor1 (Error)

● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 

E1

Sensor break of Sensor2 (Error)

● ○ ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 

E2

Pump minimum running/idle time 

● ● ● ● ● ● ● ● ● ● ● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○

Collector Minimum temperature falls below

○ ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● 

H1

Storage tank maximum temperature exceeded

○ ● ○ ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● 

H2

Collector overheating protection temp. exceeded

○ ● ○ ● ○ ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● 

H3

Collector frost protection temperature falls below

○ ● ○ ● ○ ● ○ ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● 

H4

KA_11986_ZPR-D_EN002

5

Содержание ZPR-D

Страница 1: ...Solar thermal controller ZPR D Quick installation and operating manual Firmware version 1 0x Mai 2011...

Страница 2: ...heavy current equipment Installation and maintenance have to be performed according to the corresponding safety regulations Content Commissioning 3 Mounting 3 Electrical connection 3 Operating 4 Displ...

Страница 3: ...ing time and minimum idle time is considered A two digit announcement serves the representation of the sensor temperatures and status information Commissioning Mounting The digital solar thermal contr...

Страница 4: ...s switched off in rotary switch position off permanently Anzeige With a green LED right hand the working condition of the ZPR D is indicated Mistake states are shown with sparkling in different mark s...

Страница 5: ...ollector temperature of 130 C with a hysteresis by 20 K Actual pump running idle time The solar pump CP1 is switched on by presentation of the thermal switch condition described on top on at least 1 m...

Страница 6: ...routes the heating circiut return flow about the storage tank if the storage tank temperature SF1 is higher around the adjusted temperature threshold lower rotary switch than the heating circiut retur...

Страница 7: ...d shipping Type of protection IP 40 according to IEC 529 Protection class II according to VDE 0106 Pollution degree 2 according to VDE 0110 Overvoltage category II according to VDE 0110 Humidity class...

Страница 8: ...KT Elektronik GmbH Berlinickestrasse 11 12165 Berlin Telefon 030 79 08 05 0 Telefax 030 79 08 05 20 e mail info kt elektronik de Internet http www kt elektronik de KA_11986_ZPR D_EN002 05 2011...

Отзывы: