9.3 Communication module KOM232M
The connector for the
optional
communication module KOM232M (Mat-No. 11989) is
located on the left side (front panel view) inside the controller housing (RJ45 connector).
The communication module KOM232M allows the connection of a dial up modem to the
controller.
A dial up modem is required when connecting the controller to the telecommunication
network. This way, the controller operates autonomously and is enabled to send a call to
the building control system (BCS) in case of failures. Additionally, the BCS can call the
controller to read it out and to send new data providing the valid access code after
having written the holding register No. 40145.
Note: Once the holding register No. 40145 has been written for three consecutive times
accessed with an invalid code, the controller cuts the modem connection immediately
and generates an error message "Err 7" (Unauthorized access). Therewith a call to the
configured building control system as well as an SMS delivery are triggered. Bit D6 is
deleted as soon as the error status register is read out by the building control system
and the connection is terminated.
T
he function
modem dial up blocking
can be selected in special cases in order to
suppress dial ups to report failures. With the function
modem dial up on corrected
failures
the BCS is additionally informed if a previously reported failure no longer exists.
By using the
automatic modem configuration function,
the modem connected to the
controller needs no further configuration; this is done automatically by the controller.
Functions
FS
Configuration
Modbus
1
CO6 -> F01 – 1
Modbus with 16-bit addressing
0
CO6 -> F02 – 1
Modem function
0
CO6 -> F03 – 1
Automatic modem configuration
0
CO6 -> F04 - 1
Blocking the BCS dial up
0
CO6 -> F05
BCS dial up on corrected failures
0
CO6 -> F06
Control system monitoring
0
CO6 -> F07 – 0
Setting
FS
Parameter level / Value range
Station address (ST)
255
PA6 / 1 to 247
with CO6 -> F02 - 1: 1 to 32000
Modem dialling pause (P)
5 min
PA6 / 0 to 255 min
Modem time out (T)
5 min
PA6 / 0 to 255 min
Number of dial attempts (C)
15
PA6 / 1 to 255
Phone number of the BCS (TELnr)
-
PA6 / max 22 digits; 1, 2, 3, ..., 9, 0;
„-“ End of string; „P“ Pause
EB_37383_SOL3-3_EN002
59
Содержание SOL3-3
Страница 1: ...Solar controller SOL3 3 Installation and operating manual Firmware version 1 07 April 2011...
Страница 66: ...Installation and operating manual KT Elektronik Figure 12 Mounting 66 EB_37383_SOL3 3_EN002...
Страница 86: ...Installation and operating manual KT Elektronik 86 EB_37383_SOL3 3_EN002...
Страница 87: ...KT Elektronik SOL3 3 EB_37383_SOL3 3_EN002 87...