Installation and operating manual

KT-Elektronik

Control system communication

Baud rate

The baud rate of the interface to the control system (BMS) is automatically detected and adjusted by the  ModBus-MBus-
Gateway. It will support 9600 and 19200 baud. 

Addressing

Das Modul ist  

immer

  unter der globalen Stationsadresse 254 (FE-hex) im 8-Bit-Stationsadressmodus ansprechbar. Im 

16-Bit-Stationsadressmodus  gilt die Stationsadresse 65534 (FFFE-hex).
The module is always accessible via   the global station address 254 (FE hex) in the 8-bit addressing mode. The station 
address 65534 (FFFE hex) applies to 16-bit addressing mode. 

Addressing at delivery

When delivered, a class derived from the serial number 8-bit address is set. The station address is the low two digits of the  
serial number. A special case of this rule is any serial number with significant digits "00" in this case, the station address to 
"100" set. 

Addressing by slave device TROVIS 5573, SOL3-1, SOL3-7 and WPR3

The  ModBus-MBus-Gateway automatically takes the address from the slave device. In the worst case, the acquisition of the 
station address of the slave device takes a few minutes to complete because all station addresses in the supported  
addressing modes and all supported baud rates are successively tested for recognition of a slave device. 

Address change in stand-alone operation 

Through  two holding registers may be adjusted an 8-bit station address or a 16-bit address of the ModBus-MBus-Gateway. 
The last address written determines the addressing mode of the device. 

Connection to the control system BMS

For connection to an RS485 two-wire network to a building management system BMS the ModBus-MBus-Gateway provides 
a potential free RS-485 interface with auto phase switching. The RS485 two-wire network can be connected to a two-pole 
screw terminal or to an RJ12 jack using RJ12 patch cord. Compliance with a specific polarity is not required. 

Connection to the slave device

For  connectivity  to a slave device the  ModBus-MBus-Gateway  provides an RS-485 interface through a two-pole screw 
terminal and a TTL RS-232 port via an RJ45 socket.
It is just intended to connect to one slave device. The communication parameters of slave device by the MBus ModBus 
gateway automatically calculated and applied.
A recognized slave device is indicated by the Status LED.
The station address is automatically transferred from the slave device, the station address set in the ModBus-MBus-Gateway 
is ignored.
Holding registers and coils of ModBus-MBus-Gateway and supported slave devices are located in different areas.

Connection to MBus

For connectivity to Mbus devices provides the ModBus-MBus-Gateway an interface to a two-pole screw terminal.
The MBus ModBus gateway is intended for the connection of up to 6 MBus loads.

4

EB_11997_ModBus-MBus-Gateway_EN001

Содержание ModBus-MBus-Gateway

Страница 1: ...ModBus MBus Gateway Installation and operating manual Firmware version 1 0x May 2011...

Страница 2: ...ices Only qualified personnel that is familiar with installation and commissioning of this product is allowed to mount the device and put it into operation Appropriate shipping and storage are assumed...

Страница 3: ...ead cyclically via MBus from meters and stored in an internal memory of the ModBus MBus Gateway A control system can read the last temporarily stored meter data via Modbus from the ModBus MBus Gateway...

Страница 4: ...s change in stand alone operation Through two holding registers may be adjusted an 8 bit station address or a 16 bit address of the ModBus MBus Gateway The last address written determines the addressi...

Страница 5: ...he operation of slave device To indicate operating state and function are 10 luminous dots LEDs are located on the front panel of the ModBus MBus Gateway LED status An LED lights up when the value spe...

Страница 6: ...ing the software BootManager In this case the ModBus MBus Gateway provides a transparent connection between BootManager and slave device Configuration using 5012Config For the configuration of the con...

Страница 7: ...g voltage 85 to 250 V 48 to 62 Hz max 1 8 W Ambient temperature 0 to 40 C operation 10 C to 60 C storage and transport Type of protection IP 20 according to IEC 529 Protection class II according to VD...

Страница 8: ...ronik GmbH Berlinickestrasse 11 12165 Berlin Germany Telephone 030 79 08 05 0 Telefax 030 79 08 05 20 E mail info kt elektronik de Internet http www kt elektronik de EB_11997_ModBus MBus Gateway_EN001...

Отзывы: