Installation and Operation Manual 23
7.4.4 Working parameters
Interface
Description
-- Working parameters--
→1:Starting-up voltage
2:Starting-up timelag
3:Low voltage of
electric network
Press UP/DOWN button to move
corresponding options, press ENTER to
enter into the selected menu; return back
setup interface (refer to 7.4) by pressing
ESC, there are 6 options in total, including
starting-up voltage, starting-up timelag,
low voltage of electric network, high
voltage of electric network, low
frequency of electric network and high
frequency of electric network.
7.4.4.1 Starting-up voltage
Interface
Description
---START-UP VOLT---
Input:
350V
Unit:
V
Press UP/DOWN to increase or
decrease the input figure, move the
cursor
backwards
and
confirm
completion of input as well as enter into
interface of please starting-up again
(refer to 7.4.4.7) by pressing ENTER
button, press ESC to move the cursor
frontward and return back working
interface (refer to 7.4.4); the input figure is
between 350 and 850, default is 350.
7.4.4.2 Starting-up timelag
Interface
Description
-- START-UP DELAY--
Input:
60
Unit:
Second
Press UP/DOWN to increase or
decrease the input figure, confirm input
and enter into interface of please starting-up
again (refer to 7.4.4.7) by pressing ENTER
button; press ESC to cancel input and return
back working interface (refer to 7.4.4), input
figure is between 60 and 300. This
parameter is changed by grid standards.