Drg No. KSR98202-IS-A
KSR Lighting Ltd, Unit E Hazleton Interchange, Lakesmere Road, Horndean, Hampshire, PO8 9JU
25.03.2022RTG
Installation Sheet
KSR98202
Read these instructions before commencing installation. Please give these instructions to the owner/occupier after
installation to retain for future reference/maintainence.
Navara HBX
Available finish: Black Finish
LED Highbay
KSR Lighting Aftersales: 023 92 674343
E-mail: [email protected]
Important Information
It is recommended that these luminaires are installed and fitted by a qualified electrician ensuring the installation
complies with current IEE wiring regulations & local building control. These products are designed for connection to
a 240V~50Hz supply.
Any faulty, broken or damaged luminaires should be replaced immediately.
KSR will not accept responsibility for any claims arising from a poor installation.
Please Note: The limited warranty shall be deemed null and void in the following circumstances: Failure by the
installer, end user or any third party to exercise caution to protect any covered product or part from outside
damage, adverse temperature (normal operating ambient temperature -20 - 40°C), humidity conditions, fluctuations
in the electrical system or physical abuse as well as failure related to workmanship in the installation of the products
or parts.
Important User Advice
Always switch off mains supply before fitting or servicing.
This luminaire is suitable for indoor use only and should not be fitted to damp or wet surfaces such as freshly
plastered or painted surfaces.
Do not use Megger or similar high voltage instruments. Due to the fact this luminaire contains electronic
components that maybe damaged by high test voltages, they must be disconnected from the circuit before testing.
To prevent damage to the luminaire, do not mix with conventional magnetic ballasts on the same electrical circuit.
At the end of life the luminaire is classed as WEEE under directive 2014/30/EU and should be disposed of in
accordance with local legislation.
Installation Procedure
Isolate Mains before Installation
Eye Hook Suspension Option
Using the Suspension Eye hook provided and suitable suspension method, ensure screw lock on eye hook is fully
tightened before proceeding to wire luminaire to mains.
Connect mains supply cable to Mains Supply (L,E,N)
Turn on Mains and Test Luminaire
Surface Mounting Bracket (KSR98210) Option
For Mounting Bracket option using fixings provided to secure the bracket to the high bay, ensure fixings are fully
tightened before mounting onto mounting surface. When bracket is secure proceed to wire luminaire to mains.
Connect mains supply cable to Mains Supply (L,E,N)
Turn on Mains and Test Luminaire.
If using optional KSR98203 sensor accessory please turn over for installation and operation instruction using the
KSR98204 Remote Programmer.
Lamp Details
26555
4000K
Navara HBX 200w
200W
KSR98202
Lumens
Colour
Dimensions L x H
Description
Wattage
Product Code
The light source of this luminaire is not replaceable; when the light source reaches its end of life the
light source and control gear shall be replaced
320mm DIA x 112mm
200W
IP65/IK10
0.5m
240V~50Hz
These fittings are Class I and must be Earthed
This product contains a light source of energy efficiency class D
*Please note: Depending on the amount of LED fittings on a circuit you may have to
upgrade the breaker to a 'C' or 'D' type due to the way electronic LED drivers start up with
higher inrush currents compared to HID lighting.
320.0mm