- 14 -
Press ”
▼
” to proceed to the next parameter you wish to change – or press the ”START-UP” and the
“MENU” keys at the same time to finish.
6.10 Ashscrew.
The ashscrew of a KSM boiler is monitored and controlled by Motor 3, in relation to the stoker screw.
By operating in a percentage relationship with the stoker screw, the ashscrew will automatically run more
when the stoker is in Step 3, than when the stoker is in Step 1.
The ashscrew is adjusted according to the actually combusted fued type and, therefore, it should be
adjusted so that the ashpit in the boiler bottom is half full most of the time.
If the ashscrew runs too much, the ashes are too hot when they are conveyed into the ashpit.
ASHSCREW
Press ”MENU”
ASHSCREW
MOVING FLOOR on
ADJUST 85 %
Use the arrow keys to select the ashscrew running period in percentage of the stoker screw, select a value
between 1 and up to 255%.
After selection of the wanted proportion in % press ”MENU”, and your choice has been saved.
Press ”
▼
” to proceed to the next parameter you wish to change – or press the ”START-UP” and the
“MENU” keys at the same time to finish.
6.11 Moving Floor ON.
The moving floor and the boiler cleaning system (if mounted) are activated during the set number of
seconds. This period must always be shorter than the time needed for the moving floor to run all the way
forward and all the way home, otherwise the moving floor will run several times right after each other
during each activation.
By boilers with automatic fluetube cleaner, this should be set close to maximum.
MOVING FLOOR on
Press ”MENU”
MOVING FLOOR on
MOVING FLOOR off
ADJUST 005 SEC
Use the arrow keys to select the moving floor activation period, selection from 0 to 255sec.
After selection of the wanted period, press ”MENU”, and your choice has been saved.
Press ”
▼
” to proceed to the next parameter you wish to change – or press the ”START-UP” and the
“MENU” keys at the same time to finish.
6.12 Moving floor OFF.
The period of time to be set between the activations of the moving floor and the boiler cleaning system (if
mounted) fully depends on the actually used fuel type.
By fuel producing a lot of ashes and clinker we recommend to let the system run approx. every 20
th
minute, and by woodpellets and similar fuels only once per hour, or even with longer intervals.
MOVING FLOOR off
Press ”MENU”
MOVING FLOOR
offTRANSPORT SC on
ADJUST 020 min
Содержание KSM-Multistoker 575-50
Страница 3: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 50: ......
Страница 51: ......
Страница 52: ......
Страница 53: ......
Страница 61: ... 44 Supplement C ...
Страница 62: ... 45 ...
Страница 63: ... 46 ...
Страница 64: ... 47 ...
Страница 66: ......
Страница 67: ......
Страница 68: ......