5 Installation at Site
19 of 72
Sewatec (60 Hz)
5 Installation at Site
5.1 Safety regulations
DANGER
Improper installation in potentially explosive atmospheres
Damage to the pump set!
▷
Comply with the applicable local explosion protection regulations.
▷
Observe the information given in the data sheet and on the pump/motor name
plates.
5.2 Checks prior to installation
Place of installation
WARNING
Installation on a mounting surface which is unsecured and cannot support the
load
Personal injury and damage to property!
▷
Observe the required compressive strength class C12/15 of the concrete in
exposure class XC1 as per EN 206-1.
▷
The mounting surface must be set, flat, and level.
▷
Observe the weights indicated.
1.
Check the structural requirements.
All structural work required must have been prepared in accordance with the
dimensions stated in the outline drawing/general arrangement drawing.
5.3 Installing the pump set in a horizontal position
L
1
3
2
Fig. 3:
Installation on a foundation with chemical anchors
L
Anchor-to-anchor distance
1
Shim
2
Shim for anchor-to-anchor distance
≥ 31.5 inches (800 mm)
3
Chemical
anchor
ü
The foundation has the required strength and characteristics.
ü
The foundation has been prepared in accordance with the dimensions given in
the outline drawing/general arrangement drawing.
1.
Position the pump set on the foundation and align it with the help of a spirit
level placed on the shaft and discharge nozzle.
Permissible deviation: 0.0079 inch/m (0.2 mm/m).
2.
Use shims (1) for height compensation, if necessary.
Always fit shims immediately to the left and right of the chemical anchors (3)
between the baseplate/foundation frame and the foundation itself.
For a bolt-to-bolt clearance (L) ≥ 31.5 inches (800 mm) fit additional shims (2)
halfway between the adjoining holes.
All shims must lie perfectly flush.