5 Installation at Site
20 of 68
Multitec A SX
5 Installation at Site
5.1 Safety regulations
DANGER
Improper installation in potentially explosive atmospheres
Explosion hazard!
Damage to the pump set!
▷
Comply with the applicable local explosion protection regulations.
▷
Observe the information in the data sheet and on the name plates of pump and
motor.
For positioning, installing and operating sprinkler pumps, generally comply with the
following fire protection standards and directives:
▪
VDS CEA 4001
▪
CEA 4001
▪
EN 12845
▪
NFPA 20
▪
FM GLOBAL
5.2 Checks to be carried out prior to installation
Place of installation
WARNING
Installation on foundations which are unsecured and cannot support the load
Personal injury and damage to property!
▷
Make sure the foundation concrete is of sufficient strength (min. C12/15 to
DIN 1045).
▷
Only place the pump set on a foundation whose concrete has set firmly.
▷
Only place the duckfoot bend on horizontal and level surfaces.
▷
Refer to the weight given in the general arrangement drawing.
1.
Check the structural requirements.
All structural work required must have been prepared in accordance with the
dimensions stated in the outline drawing/general arrangement drawing.
5.3 Installing the pump set
CAUTION
Warped baseplate or pump
Damage to the pump!
▷
Align the baseplate and the pump accurately and carefully when installing the
pump set.