6.2.4 Fluid handled
6.2.4.1 Permissible fluids to be handled
▪
Clean fluids not chemically or mechanically aggressive to the pump materials
▪
Drinking water
▪
Service water
▪
Cooling water
6.2.4.2 Fluid temperature
Table 10:
Temperature limits of the fluid handled
Permissible fluid temperature
Value
Maximum
+70 °C
Minimum
0 °C
6.2.5 Minimum flow rate
Table 11:
Minimum flow rate per pump in manual mode
Size
Minimum flow rate per pump
[l/h]
Movitec 2B
200
Movitec 4B
400
Movitec 6B
600
Movitec 10B
1100
Movitec 15C
1900
Movitec 25B
2800
Movitec 40B
4600
Movitec 60B
6100
Movitec 90B
8500
Movitec 125B
12500