5 Valve Description
16 of 36
BOA-Control/ BOA‑Control IMS
5.3.1.1 Operating data
Table 5:
Operating properties
Characteristic
Value
Nominal pressure
PN 16
Nominal size
DN 15 - 350
4)
5)
Max. permissible pressure [bar]
16
Min. permissible temperature [°C]
≥ -10
Max. permissible temperature [°C]
≤ +120
6)
5.3.1.2 Fluids handled
▪
Hot water for heating systems, with or without glycol (≤ 60 %)
▪
Cold water for air-conditioning systems, with or without glycol (≤ 60 %)
▪
The fluid handled should meet the requirements as specified in VdTÜV/AGFW
TCh 1466 or VDI 2035.
▪
Only limited measurements of fluids containing gas or air can be made with
ultrasound equipment. Proper venting of the systems is therefore essential.
▪
Drinking water (BOA-Control EKB / BOA-Control IMS EKB models only)
▪
Service water
▪
Not suitable for steam or fluids liable to attack EPDM and the electrostatic plastic
coating.
▪
Other fluids on request.
5.3.1.3 Design details
Design
Valve:
Valves to type series booklet 7128.1
▪
BOA-Control IMS complete with sensors for measuring flow rate and
temperature
▪
BOA-Control suitable for attaching sensors for measuring flow rate and
temperature
▪
Straight-way globe valve with slanted seat
▪
Non-rotating stem with protected, external thread
▪
Non-rising handwheel
▪
Locking device, travel stop, position indicator, throttling plug and insulating cap
with anti-condensation feature as standard
▪
Compact EPDM-encapsulated throttling plug as soft main seat and back seat
▪
Maintenance-free stem seal with EPDM profile ring
▪
Face-to-face length to DIN EN 558/1
▪
Exterior coating: blue, RAL 5002
▪
The valves satisfy the safety requirements of Annex I of the European Pressure
Equipment Directive 2014/68/EU (PED) for fluids in Group 2.
Measuring computer:
▪
Measuring flow rate and temperature requires the use of a measuring computer.
▪
Mobile short-term measurement with battery-powered BOATRONIC MS
▪
Permanent measurement set-up with BOATRONIC MS-420 (24 V DC power
supply)
4)
DN 250-350: type BOA-H
5)
BOA-Control EKB / BOA-Control IMS EKB up to DN 200
6)
BOA-Control EKB / BOA-Control IMS EKB ≤ 40°C