3 Description
8 of 16
BACnet MS/TP Gateway
4
BACnet parameter DIL switch
5
Back-up battery
3.3.1 Setting jumpers
Only jumper 1 (BACnet MS/TP bus terminator) typically must be set, if required,
during commissioning.
3.3.2 DIL switch
Fig. 3:
DIL switch 4
DIP switches 1 to 7 code the master node address, and DIP switches 8 to 10 code the
baud rate in the BACnet MS/TP network.
The values are binary coded from right to left.
Table 3:
DIP switches for master node addressing
DIP switches
Master node address
1
2
3
4
5
6
7
0
0
0
0
0
0
1
1
0
0
0
0
0
1
0
2
0
0
0
0
1
0
0
4
0
0
0
1
0
0
0
8
0
0
1
0
0
0
0
16
0
1
0
0
0
0
0
32
1
0
0
0
0
0
0
64
The master node address can be set from 1 to 127 using the DIP switches. It may be
necessary to activate several switches to obtain the required address.
NOTE
Master node address 0 is invalid and deletes the current configuration on the
gateway.
Table 4:
DIP switches for setting the baud rate
DIP switches
Baud rate
8
9
10
0
0
0
4800
0
0
1
9600
0
1
0
19200
0
1
1
38400
1
0
0
56700
1
0
1
76800
1
1
0
115200
1
1
1
230400
The baud rate for the BACnet MS/TP network is set to 38400 by default.
3.3.3 Back-up battery
Insert battery of type CR2032 with the positive terminal pointing upwards. The
battery buffers the data and the real-time clock of the gateway during a power
interruption.