6 Commissioning/Start-up/Shutdown
29 of 56
Ama-Drainer 80/100
2331.823/07-EN
6.3 Shutdown/storage/preservation
6.3.1 Stopping
Ama-Drainer ... N (without float switch)
The pump set stops automatically via the control unit.
Ama-Drainer ... S (with float switch)
B
Fig. 6:
Stop level
B Stop level
The pump set stops automatically when the float switch reaches stop point B.
6.3.2 Measures to be taken for shutdown
WARNING
Unintentional starting of the pump set
Risk of injury by moving components and shock currents!
▷
Ensure that the pump set cannot be started unintentionally.
▷
Always make sure the electrical connections are disconnected before carrying
out work on the pump set.
WARNING
Fluids handled, consumables and supplies which are hot and/or pose a health
hazard
Risk of injury!
▷
Observe all relevant laws.
▷
When draining the fluid take appropriate measures to protect persons and the
environment.
▷
Decontaminate pumps which handle fluids posing a health hazard.
1. Disconnect the pump from the power supply and protect it against start-up.
2. Wait until the pump has cooled down (10 minutes), then remove it.
3. Properly flush the pump.
Point the water jet on the pump's discharge nozzle.
4. Leave the pump to dry.
5. Store the pump vertically in a dark, dry and frost-proof room.