9 Trouble-shooting
31 of 36
Calio-Therm NC
1157.881/03-EN
9 Trouble-shooting
WARNING
Improper work to remedy faults
Risk of injury!
▷
For any work performed to remedy faults, observe the relevant information
given in this operating manual and/or in the product literature provided by the
accessories manufacturer.
If problems occur that are not described in the following table, consultation with KSB
Service is required.
A
Pump is running, but does not deliver
B
Pump does not start up or pump running irregularly
C
Pump running but not delivering water
D
Noises during pump operation
Table 10:
Trouble-shooting
A B C D Possible cause
Remedy
2)
✘
-
-
- Pump not connected to power supply
Check the fuses and correct connection to power
supply. If required, disconnect the pump from the
power supply and re-connect it to the power
supply (voltage reset).
-
✘
-
- Impurities in the pump
-
✘
-
- Blockage in the pump
-
-
✘
- Shut-off elements closed
Calio-Therm S NC: Open the shut-off elements.
Calio-Therm S NCV: Open the integrated shut-off
valve.
-
-
-
✘
Pump power output too high
Select a lower speed level.
-
-
-
✘
System pressure too low
Increase the system pressure by filling more water
into the boiler.
-
-
✘ ✘
Air in the system
Vent the pump (vent plug) and system.
(
-
-
-
✘
Pump running dry
2)
Release pump set pressure before attempting to remedy faults on parts which are subjected to pressure.