INSTALLATION

Ensure that suitable fastener is used for each of the mounting holes in the panel.
Ensure that the fan panel and drive components are not bent or twisted during installation.

Fan should be installed so that any obstructions will not be within 1 Diameter of the fan inlet and outlet.
Ensure that the fan orientation is correct for the required air flow direction.

Electrical Connection

Before carrying out any installation or wiring of the range ensure that the mains electrical supply is

disconnected.

Before making any electrical connections ensure that the voltage and frequency of the mains electrical supply 
matches that of the fan data plate label (maximum permissible deviation of voltage and fre/- 5%).

All models must be wired in accordance with the enclosed instructions and the direction of rotation must be 

checked.

The earth connection must be connected and checked for continuity before leaving the installation.
In addition it is important to check that the wires within the terminal block/box are separated whereby a 

minimum of 10mm distance (at 400 volts) and that the wires are correctly and firmly tightened within the 
terminal block and that the connection box lid is required.

Impeller

All APN fans include a dynamically balanced impeller. The impellers with adjustable pitch angle have been 
factory set to the correct blade angle of operation. UNDER NO CIRCUMSTANCES MUST THE BLADE ANGLE BE 

ADJUSTED OR CHANGED, OTHER THAN BY AN KRUGER APPROVED ENGINEER.

ROUTINE MAINTENANCE

Maintenance  should  always  be  performed  by  experienced  and  trained  personnel.  Do  not  attempt  any 

maintenance on a fan unless the electrical supply has been locked out or tagged out and the impeller  has 
been secured.

Under  normal  circumstances,  handling  clean  air,  the  system  should  require  cleaning  only  about  a  year. 

However, the fan and system should be checked at regular intervals to detect any unusual accumulation.

The fan impeller should be specially checked for build-up of material or dirt which may cause an Imbalance 
with resulting undue wear on bearings and belt drives. A regular maintenance program should be established 

as needed to prevent material build-up.

Periodic inspection of the rotating assembly must be made to detect any indication of weakening of the rotor 
because of corrosion, erosion, or metal fatigue.

(For APN only)