29
Fan Powered Terminal Units IOM
Set
Point
CFM
MANUAL %
Display
(option 6)
REMOTE 0-10Vdc (0-20mA)
DC Signal (option 7)
REMOTE 2-10Vdc (4-20mA)
DC Signal (option 8)
4550
100
10
(20.0)
10
(20.0)
4505
99
9.9
(19.8)
9.9
(19.8)
4459
98
9.8
(19.6)
9.8
(19.7)
4414
97
9.7
(19.4)
9.8
(19.5)
4368
96
9.6
(19.2)
9.7
(19.4)
4323
95
9.5
(19.0)
9.6
(19.2)
4277
94
9.4
(18.8)
9.5
(19.0)
4232
93
9.3
(18.6)
9.4
(18.9)
4186
92
9.2
(18.4)
9.4
(18.7)
4141
91
9.1
(18.2)
9.3
(18.6)
4095
90
9.0
(18.0)
9.2
(18.4)
4050
89
8.9
(17.8)
9.1
(18.2)
4004
88
8.8
(17.6)
9.0
(18.1)
3959
87
8.7
(17.4)
9.0
(17.9)
3913
86
8.6
(17.2)
8.9
(17.8)
3868
85
8.5
(17.0)
8.8
(17.6)
3822
84
8.4
(16.8)
8.7
(17.4)
3777
83
8.3
(16.6)
8.6
(17.3)
3731
82
8.2
(16.4)
8.6
(17.1)
3686
81
8.1
(16.2)
8.5
(17.0)
3640
80
8.0
(16.0)
8.4
(16.8)
3595
79
7.9
(15.8)
8.3
(16.6)
3549
78
7.8
(15.6)
8.2
(16.5)
3504
77
7.7
(15.4)
8.2
(16.3)
3458
76
7.6
(15.2)
8.1
(16.2)
3413
75
7.5
(15.0)
8.0
(16.0)
3367
74
7.4
(14.8)
7.9
(15.8)
3322
73
7.3
(14.6)
7.8
(15.7)
3276
72
7.2
(14.2)
7.8
(15.5)
3231
71
7.1
(14.0)
7.7
(15.4)
3185
70
7.0
(13.8)
7.6
(15.2)
3140
69
6.9
(13.6)
7.5
(15.0)
3094
68
6.8
(13.6)
7.4
(14.9)
3049
67
6.7
(13.4)
7.4
(14.7)
3003
66
6.6
(13.2)
7.3
(14.6)
2958
65
6.5
(13.0)
7.2
(14.4)
2912
64
6.4
(12.8)
7.1
(14.2)
2867
63
6.3
(12.6)
7.0
(14.1)
2821
62
6.2
(12.4)
7.0
(13.9)
2776
61
6.1
(12.2)
6.9
(13.8)
2730
60
6.0
(12.0)
6.8
(13.6)
2685
59
5.9
(11.8)
6.7
(13.4)
2639
58
5.8
(11.6)
6.6
(13.3)
2594
57
5.7
(11.4)
6.6
(13.1)
2548
56
5.6
(11.2)
6.5
(13.0)
2503
55
5.5
(11.0)
6.4
(12.8)
2457
54
5.4
(10.8)
6.3
(12.6)
2412
53
5.3
(10.6)
6.2
(12.5)
2366
52
5.2
(10.4)
6.2
(12.3)
2321
51
5.1
(10.2)
6.1
(12.2)
Set
Point
CFM
MANUAL %
Display
(option 6)
REMOTE 0-10Vdc (0-20mA)
DC Signal (option 7)
REMOTE 2-10Vdc (4-20mA)
DC Signal (option 8)
2275
50
5
(10.0)
6.0
(12.0)
2230
49
4.9
(9.8)
5.9
(11.8)
2184
48
4.8
(9.6)
5.8
(11.7)
2139
47
4.7
(9.4)
5.8
(11.5)
2093
46
4.6
(9.2)
5.7
(11.4)
2048
45
4.5
(9.0)
5.6
(11.2)
2002
44
4.4
(8.8)
5.5
(11.0)
1957
43
4.3
(8.6)
5.4
(10.9)
1911
42
4.2
(8.4)
5.4
(10.7)
1866
41
4.1
(8.2)
5.3
(10.6)
1820
40
4
(8.0)
5.2
(10.4)
1775
39
3.9
(7.8)
5.1
(10.2)
1729
38
3.8
(7.6)
5.0
(10.1)
1684
37
3.7
(7.4)
5.0
(9.9)
1638
36
3.6
(7.2)
4.9
(9.8)
1593
35
3.5
(7.0)
4.8
(9.6)
1547
34
3.4
(6.8)
4.7
(9.4)
1502
33
3.3
(6.6)
4.6
(9.3)
1456
32
3.2
(6.4)
4.6
(9.1)
1411
31
3.1
(6.2)
4.5
(9.0)
1365
30
3
(6.0)
4.4
(8.8)
1320
29
2.9
(5.8)
4.2
(8.6)
1274
28
2.8
(5.6)
4.2
(8.5)
1229
27
2.7
(5.4)
4.1
(8.3)
1183
26
2.6
(5.2)
4.0
(8.2)
1138
25
2.5
(5.0)
3.9
(8.0)
1092
24
2.4
(4.8)
3.8
(7.8)
1047
23
2.3
(4.6)
3.8
(7.7)
1001
22
2.2
(4.4)
3.6
(7.5)
956
21
2.1
(4.2)
3.7
(7.4)
910
20
2
(4.0)
3.6
(7.2)
865
19
1.9
(3.8)
3.5
(7.0)
819
18
1.8
(3.6)
3.4
(6.9)
774
17
1.7
(3.4)
3.4
(6.7)
728
16
1.6
(3.2)
3.3
(6.6)
683
15
1.5
(3.0)
3.2
(6.4)
637
14
1.4
(2.8)
3.1
(6.2)
592
13
1.3
(2.6)
3.0
(6.1)
546
12
1.2
(2.4)
3.0
(5.9)
501
11
1.1
(2.2)
2.9
(5.8)
455
10
1
(2.0)
2.8
(5.6)
410
9
0.9
(1.8)
2.7
(5.4)
364
8
0.8
(1.6)
2.6
(5.3)
319
7
0.7
(1.4)
2.6
(5.1)
273
6
0.6
(1.2)
2.5
(5.0)
228
5
0.5
(1.0)
2.4
(4.8)
182
4
0.4
(0.8)
2.3
(4.6)
137
3
0.3
(0.6)
2.2
(4.5)
91
2
0.2
(0.4)
2.2
(4.3)
46
1
0.1
(0.2)
2.1
(4.2)
CFM VALUES BELOW RECOMMENDED MINIMUM MAY AFFECT LIFE OF MOTOR.
TABLE 21: QFC Size 7 ECM CALIBRATION
Содержание KLPP
Страница 49: ......