Quick Installation Guide 

– Mult-K Revision 3.2 – June, 2020 

Quick Installation Guide

 

 

❹Voltage Input Connections 

Connect phases and neutral references to the 

  

terminal block, using the order described below:  
 

Terminal Description  Signal to be Connected 

              4 – N 

Neutral 

3 – Va 

Phase ‘R’ 

2 – Vb 

Phase ‘S’ 

1 – Vc 

Phase ‘T’ 

Measurement Range: 20 to 500Vac Ph-Ph 

11,54 to 288,67 Vac Ph-N

 

 

❺ Current Input Connections 

Connect phase references to the 

Ⓘ 

terminal  

block, using the order described below:

 

 

 

Terminal Description  Signal to be Connected 

10 – °Ia  

CT’s S1 - Phase ‘R’ 

9 – Ia 

CT’s S2 - Phase ‘R’ 

8 – °Ib 

CT’s S1 - Phase ‘S’ 

7 – Ib 

CT’s S2 - Phase ‘S’ 

6 – °Ic 

CT’s S1 - Phase ‘T’ 

5 – Ic 

CT’s S2 - Phase ‘T’ 

Measurement Range: 20mA to 5Aac 

(Continuous Overload: up to 7.5Aac)

 

 

❻Accessing Operation Modes

 

 

Instantaneous Measurements: 

checking 

of 

V, A, W, VAr, VA, PF

 and 

Hz 

values. To 

access  this  mode,  hold  the     

  and  

  keys  simultaneously      for  three 

seconds.

 

 

 

 

Energy  Measurements: 

checking  of 

kWh+,  kWh-,  kVArh+,  kVArh-,  kW 

and

  

kVA 

values. 

  

To access this mode, hold 

the   

 and  

 keys simultaneously   

for three seconds.

 

 

 

 

 

Function (Configurations): 

configuration 

of  constants  for  PT  and  CT,  connection 
diagrams,  integration  time  (demand), 
communication  parameters  and  reset 
command  (energies  and  demands).  To 

access this mode, hold the  

 and 

 

keys simultaneously for three seconds. 

❼ Configuring the Product 

 

 

The  first  step  is  to  access  Function 

mode, by holding the 

and

keys 

simultaneously until the message

 

Fun

 

appears  in  L1.  Then,  to  navigate 

through  menus  use

or

  keys

To  enter  a  specific  menu,  use 

key.

 

 

 

PT  Configuration:

  Definition  of 

Potential Transformer ratio.  
Example:  440/220V,  PT=  0002.00. 

Use 

 key 

to navigate 

through

 the 

digits and 

 

to increment or 

decrement  the  value  of  the  active  
digit. If no PT is used, PT ratio must 

be 0001.00 

 

 

CT  Configuration:

  Definition  of 

Current Transformer ratio. 
Example: 500/5A, CT = 0100.00.  

Use 

 key 

to navigate 

through

 the 

digits and 

 

to increment or 

decrement  the  value  of  the  active  
digit. If no CT is used, CT ratio must 

be 0001.00 
 

CD  Configuration:

  Definition  of 

Connection  Diagram,  according  to 
the circuit measured.  

Use 

 key 

to navigate 

through

 the 

digits and 

 

to increment or 

decrement  the  value  of  the  active 
digit. Please refer to the “Connection 

Diagrams” table for checking the available CD options. 
 

To  confirm  a  configured  value,  press              till  all  digits  stop 
flashing,  only  the  LEDs  ‘k’  and  ‘M’  will  be  blinking  in  this 
situation. 

 