Setting the high-fire rate:

  • 

 Set the air and gas circuit of the burner to high 

fire while continuously monitoring the flame.

 

Avoid CO formation – always operate the burner 

with excess air when starting up!

 

When the desired maximum valve positions are 

reached, set the gas pressure p

gas

 using the 

restrictor upstream of the burner.

p

gas

0

p

atm.

p

0

p

2

p

1

Re-adjusting the air flow rate:

  • 

 Check the air pressure p

air

 on the burner and 

adjust using the air restrictor if required.

  • 

 When using air restricting orifices: check the air 

pressure p

air

 and rework the orifice if required.

 DANGER

Risk of explosion and poisoning during burner 
adjustment with an air deficiency!

 Adjust the 

gas and air supply so that the burner is always oper-
ated with excess air – otherwise CO will form in the 
furnace chamber. CO is odourless and poisonous! 
Conduct a flue gas analysis.

  • 

 Measure the gas and air flow rates if possible. 

Determine the lambda value and re-adjust the 
settings if required.

Tightness test

 DANGER

To ensure that there is no danger resulting from a 

leak, check the gas connections on the burner for 
leaks immediately after the burner has been put 
into operation.

1

 

Avoid condensation due to the furnace atmos-

phere entering the burner housing. While the 
burner is switched off, at furnace temperatures 
above 500°C (932°F), it must be cooled with a 
low air volume – see page 9 (Cooling air).

Cooling air

 

While the burner is switched off and depending 
on the furnace temperature, there must be a cer-
tain air flow for cooling the burner components.

700 800 900 1000 1100 1200 1300 1400

0

6

4

2

5

3

1

0

12

8

4

10

6

2

ZIO

ZIO..KB..E

ZIO..K

Furnace temperature 

[

°C

]

Cooling air at 20°C,

air volume at rated capacity 

 [%]

Cooling air at 450°C,

air volume at rated capacity 

 [%

]

 

Diagram: the relative air volume in percentage 
values, based on the air volume for the rated ca-
pacity of the relevant size, is given in the diagram. 
For hot air (450°C), the values on the right-hand 
axis are based on the standard air volume for 
the relevant rated capacity.

 

Leave the air fan switched on until the furnace 
has cooled down completely.

Blocking and recording the settings
  

 Produce a measurement report.

  

  Set the burner to low fire and check the settings.

 

 

  Set the burner to low and high fire several times 

while monitoring the pressure settings, flue gas 
values and flame patterns.

 4 

 Remove the measuring devices and close off 

the test nipples – tighten the grub screws.

 5 

 Block and seal the adjusting elements.

 6 

  Induce a flame failure, e.g. by pulling the plug off 

the ionization electrode. The flame detector must 
close the gas safety valve and signal a fault.

 7 

  Switch the system on and off several times while 

monitoring the automatic burner control unit.

 8 

 Produce an acceptance report.

 DANGER

An incorrect change of the burner settings may 

change the gas/air ratio and lead to unsafe oper-
ating conditions. Risk of explosion in case of CO 
being formed in the furnace chamber! CO is odour-
less and poisonous!

Содержание ZIO 165

Страница 1: ...Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 11 11 The following chapters have been changed Checking the usage Installation Preparing commissioning Technical data Logistics Declaration of Incorporation Operating instructions D GB GB 1 Translation from the German 032...

Страница 2: ...ternal insulation 165 200 Burner size R H K Normal flame Long soft flame Flat flame B D G M Natural gas Coke oven gas town gas Propane propane butane butane Propane propane butane butane L Ignition lance 50 100 150 200 Burner tube length mm 35 135 235 Position of burner head mm 1 to 199 1E to 199E Burner head identifier High temperature version A to Z Construction stage Z Special version Part desi...

Страница 3: ...rning in an open combustion chamber Control High Low High Low Off continuous Type of burner head H Max capacity approx 80 depending on the outlet diameter of the burner quarl Medium to high flow velocity Flat flame burner quarl For industrial furnaces and kilns and for burning in an open combustion chamber Control High Low High Low Off continuous limited control range Type of burner head K Capacit...

Страница 4: ... units to prevent mechanical stress or transmission of vibration Ensure that the seals are undamaged DANGER Risk of explosion Ensure the connection is gas tight For connecting to ANSI NPT connections An adapter set is required for connection to ANSI NPT see page 12 Accessories Type Gas connection GA Air connection LA ZIO 165 1 11 5 NPT 4 57 ZIO 200 2 11 5 NPT 6 72 Flange hole diameter Weld flange ...

Страница 5: ...ion cable see automatic burner control unit operating instructions Connect the ionization electrode to the automatic burner control unit via the ionization cable Ignition electrode Z Length of ignition cable max 5 m 15 ft recom mended 1 m 40 For permanent ignition max ignition cable length 1 m 40 Lay the ignition cable individually and not in a metal conduit Install the ignition cable separately f...

Страница 6: ...st volume into the furnace chamber Determining the flow rates QGas PB Hu QLuft QGas λ Lmin QGas Gas flow rate in m3 h ft3 h PB Burner capacity in kW BTU h Hu Gas calorific value in kWh m3 BTU ft3 QLuft Air flow rate in m3 n h scfh λ Lambda air index Lmin Minimum air requirement in m3 n m3 n scf scf Use the lower calorific value Hu Information on the gas quality supplied can be obtained from the co...

Страница 7: ...xternaldia 9mm 0 35 patm pair 0 3 5 2 4 L Loosen the screw 2 turns Fully open the air supply patm pair 0 5 Low fire The burner must only be ignited at low fire be tween 10 and 30 of the rated capacity Qmax see type label Reduce the air supply on the air control valve and set the desired low fire rate e g using a limit switch or mechanical stop On air control valves with bypass the bypass orifice s...

Страница 8: ...n adjustable gas restrictor be installed upstream of the burner open the restrictor by approx a quarter Open the gas supply Ignite the burner The safety time of the automatic burner control unit starts to elapse If no flame forms check and adjust the gas and air pressures of the start gas adjustment In the case of operation with bypass e g when using an air gas ratio control check the bypass nozzl...

Страница 9: ... Cooling air While the burner is switched off and depending on the furnace temperature there must be a cer tain air flow for cooling the burner components 700 800 900 1000 1100 1200 1300 1400 0 6 4 2 5 3 1 0 12 8 4 10 6 2 ZIO ZIO KB E ZIO K Furnace temperature C Cooling air at 20 C air volume at rated capacity Cooling air at 450 C air volume at rated capacity Diagram the relative air volume in per...

Страница 10: ...ark plug 1 using the dowel pin 2 10 Adjust spark plug and electrode to the measured total length L 11 12 Turning the spark plug makes it easier to feed the electrode into the burner insert Checking the burner 16 13 14 15 If the burner insert is dismantled the gas housing gasket will have to be renewed 17 Place the burner insert in a safe place Depending on the amount of dirt or wear replace the ig...

Страница 11: ...t of malfunction DANGER Electric shocks can be fatal Before working on possible live components ensure the unit is discon nected from the power supply Risk of injury Burner heads have sharp edges Fault clearance must only be undertaken by author ized trained personnel If no fault is detected when checking the burner proceed to the automatic burner control unit and check for faults in accordance wi...

Страница 12: ...d setting Order number 05012009 Adapter set 8 8 For connecting ZIO to NPT ANSI connections Burner Adapter set Order No ZIO 165 BR 165 NPT 74922636 ZIO 200 BR 200 NPT 74922637 Nozzle set Available on request for connecting integrated ignition lances to NPT threads Technical data Gas supply pressure approx 20 to 50 mbar air supply pressure approx 25 to 40 mbar each depending on flame shape gas type ...

Страница 13: ...as Description Burner for gas Typenbezeichnung Type BIO BIOA ZIO BIC BICA ZIC BIOW ZIOW BICW ZICW Anhang I Artikel Annex I Article 1 1 3 1 1 5 1 3 2 1 3 4 1 5 2 1 7 4 Folgende harmonisierte Normen wurden angewandt The following harmonized standards have been applied Lotte Büren Sandra Runde Datum Date Konstrukteurin Designer Sandra Runde ist bevollmächtigt die speziellen technischen Unterlagen gem...

Страница 14: ...ns please contact your local branch office agent The addresses are available on the Internet or from Elster GmbH We reserve the right to make technical modifications in the interests of progress info kromschroeder com www kromschroeder com Contact Certification Approval for Russia Certified by Gosstandart under Technical Regulations Approved by Rostekhnadzor RTN ...

Отзывы: