PFA 70 in conjunction with PFU 780..L

Parameter 43 = 3

 4 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 01

.

 

The PFUs start the burner pre-purge procedure.

 WARNING

The pre-purge duration is not included in the program. 

Pre-purge until the combustion chamber has been ad-
equately ventilated.

 5 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 02

.

 

The PFUs start the pilot burners.

 6 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 03

.

 

The PFUs start the main burners, the pilot burners 

remain switched on.

 7 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 00

.

 

The PFUs switch off all the burners.

 

By pressing the Reset/Information button repeatedly, 
the PFUs are activated to switch between pre-purge 
(the display indicates step 

 01

), pilot burner start (the 

display indicates step 

 02

), main burner start (the 

display indicates step 

 03

) or burner off (the display 

indicates step 

 00

).

High/Low operating mode
PFA 700 in conjunction with PFU 760..L

Parameter 43 = 4

 4 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 01

.

 

The PFUs start the burner pre-purge procedure.

 WARNING

The pre-purge duration is not included in the program. 

Pre-purge until the combustion chamber has been ad-
equately ventilated.

 5 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 03

.

 

The PFUs start the burners.

 6 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 04

.

 

The PFUs 760..L activate the external air valves, the 

burners switch to high-fire rate.

 7 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 03

.

 

The PFUs 760..L deactivate the external air valves, 

the burners switch to low-fire rate.

 

Each time the Reset/Information button is pressed, the 
air valves are opened (the burners switch to high-fire 
rate, the display indicates 

 04

) or closed (the burn-

ers switch to low-fire rate, the display indicates 

 03

).

PFA 70 in conjunction with PFU 780..L

Parameter 43 = 4

 4 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 01

.

 

The PFUs start the burner pre-purge procedure.

 WARNING

The pre-purge duration is not included in the program. 

Pre-purge until the combustion chamber has been ad-
equately ventilated.

 5 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 02

.

 

The PFUs start the pilot burners.

 6 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 03

.

 

The PFUs start the main burners, the pilot burners 

remain switched on.

 7 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 04

.

 

The PFUs 780..L activate the external air valves, the 

main burners switch to high-fire rate.

 8 

  Press the Reset/Information button for 1 s.

 

The display indicates step 

 03

.

 

The PFUs 780..L deactivate the external air valves, 

the main burners switch to low-fire rate.

 

Each time the Reset/Information button is pressed, the 
air valves are opened (the burners switch to high-fire 
rate, the display indicates 

 04

) or closed (the burn-

ers switch to low-fire rate, the display indicates 

 03

).

Faults

 DANGER

Electric shocks can be fatal! Before working on possible 
live components, ensure the unit is disconnected from 
the power supply.
Fault-clearance must only be undertaken by authorized, 
trained personnel.

 

Faults may be cleared only using the measures de-
scribed below.

 

If the PFA does not respond even though all faults 
have been remedied: remove the unit and return it to 
the manufacturer for inspection.

 ? 

 

Faults

 ! 

 

Cause

 • 

 

Remedy

 ? 

  

The 7-segment display does not light up.

 ! 

   Mains voltage is not applied.

 • 

  Check the wiring, apply mains voltage (see type label).

Содержание BGT SA-8U/1DP

Страница 1: ...NING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 06 13 The following chapters have been changed BGT SA 9U 1D...

Страница 2: ... Part designations 2 6 1 3 4 6 7 5 8 1 LED display for program status and error messages 2 Reset Information button 3 On Off button 4 Type label 5 Connection for opto adapter 6 Screws for attachment to the subrack 7 Code switches for address setting 8 CD with device master data GSD file Input voltage and ambient temperature see type label PFA 700 BGT SA 9U 1DP Pre wired module subrack for a fieldb...

Страница 3: ...ram Setting the PFA All the unit specific parameters for the PFA are saved in a device master data file GSD file see www docutheck com 1 Copy device master data for the PFA into the program mable logic controller PLC The steps required to copy the file are described in the instructions for the PLC 2 Configure the PROFIBUS DP using the appropriate tools for the PLC you are using The PFA will automa...

Страница 4: ... A P DI on on on PFU 7 2 3 3 4 1 2 PFU 2 1 2 PFU 4 1 2 PFU 6 1 2 PFU 8 4 5 1 2 PFU 2 1 2 PFU 4 1 2 PFU 6 1 2 PFU 8 1 2 ϑ A P A P DI on on on PFA 6 1 2 ϑ A P A P DI on on on PFU 2 1 2 ϑ A P A P DI on on on PFU 4 1 2 ϑ A P A P DI on on on PFU 6 1 2 ϑ A P A P DI on on on PFU 8 7 Legend 1 2 ϑ A P A P DI on on on Ready for operation 1 2 ϑ A P A P DI on on on Burner start up signal 1 2 Start up signal p...

Страница 5: ... in manual mode the PFA switches back to normal operation automatically When using operating mode parameters set at the factory PFA 700 PFA 710 Parameter 43 1 4 Press the Reset Information button for 1 s The display indicates step 04 The PFUs start the burners and open the air valve via the external control system programming of the operating mode at the factory When using adjusted operating mode ...

Страница 6: ...ers switch to low fire rate Each time the Reset Information button is pressed the air valves are opened the burners switch to high fire rate the display indicates 04 or closed the burn ers switch to low fire rate the display indicates 03 PFA 710 in conjunction with PFU 780 L Parameter 43 4 4 Press the Reset Information button for 1 s The display indicates step 01 The PFUs start the burner pre purg...

Страница 7: ...al mode Switch the PFA to normal operation The display indicates Profibus module fault Remove the unit and return it to the manufacturer The display indicates 30 31 34 80 89 94 95 96 97 98 or 99 Internal faults Remove the unit and return it to the manufacturer Technical data BGT Weight 2 3 kg PFA Front width 8 depth units 40 6 mm Overall height 3 height units 128 4 mm Ambient temperature 20 C to 6...

Страница 8: ...2e 4e 2c 4c sk1 PFU 7xx v2 v1 6a 6e c1 c2 10c 12c 10a 12a 30e 22a 2 1 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a l Z I 1 26e 30a 32c 230 V F1 s PFU c1 c2 10c 12c 10a 12a 30e 22a 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a Z I 1 1 1 1 2 3 4 5 6 X9 7 8 DI 2 X10 21 X1 3 X1 5 UVS 1 2 3 X10 21 GB 8 GB F NL I E BGT SA 9U 1DP connection diagram ...

Страница 9: ...Vex 24 Vex 1 2 3 4 1 2 3 4 14b 18b 21b 22b 23b 24b I O 18c N PE 24 Vex 0 Vex 19b 20b 1 2 3 4 5 6 7 8 9 10 X10 11 12 13 30e 14 17 18 19 20 21 22 X10 K2 K1 COM k2 k3 k5 k4 E1 E2 E3 E4 P 30c PFU 19c 17b 24 V L1 PROFIBUS DP 25b 26b K4 K5 K3 24 Vex 24 Vex 24 Vex max 1 A 24 V PROFIBUS DP PFU 7xx 1 9 1 22e 16c 18e 2a 4a 2e 4e 2c 4c sk1 U 7xx v2 v1 6a 6e 2 1 l DI 2 15 16 1 2 3 4 5 6 X1 7 8 k1 GB 9 D GB ...

Страница 10: ... v2 v1 6a 6e c1 c2 10c 12c 10a 12a 30e 22a 2 1 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a l Z I 1 26e 30a 32c 230 V F1 s PFU c1 c2 10c 12c 10a 12a 30e 22a 1 2 28c 26a 14a 14e 10e 12e 24c 20c 18a Z I 1 1 1 1 2 3 4 5 6 X8 7 8 DI 2 X8 3 X8 5 UVS 1 2 3 X10 21 X1 3 X1 5 UVS 1 2 3 X10 21 GB 10 GB F NL I E BGT SA 8U 1DP connection diagram ...

Страница 11: ...b I O 17c N PE 24 Vex 0 Vex 19b 20b 1 2 3 4 5 6 7 8 9 10 X10 11 12 13 30e 14 17 18 19 20 21 22 X10 K2 K1 COM k2 k3 k5 k4 E1 E2 E3 E4 P 30c PFU 19c 17b 24 V L1 PROFIBUS DP 25b 26b K4 K5 K3 24 Vex 24 Vex 24 Vex max 1 A 24 V PROFIBUS DP PFU 7xx 1 8 1 22e 16c 18e 2a 4a 2e 4e 2c 4c sk1 U 780 v2 v1 6a 6e 2 1 l DI 2 15 16 1 2 3 4 5 6 X1 7 8 2 1 1 2 1b 1 PFU 7 PFU 7b 27a 8 PFU 27c 27b 24a 26a 1 PFU 2 PFU ...

Страница 12: ...ations to the Profibus bus ca ble To replace existing PROFIBUS plug connectors if a new PFA 700 is operated in an old module subrack with the Order No 84402283 in order to improve EMC see page 4 Replacing the PFA 5 5 15 A B A B O N O F F Data cable fold back the woven shield A and B incoming cables A and B outgoing cables 1st and last stations ON other stations OFF Data cables A and B must not be ...

Отзывы: