background image

GB-3

D

GB

F

NL

I

E

Wiring

  

  Disconnect the system from the electrical power 

supply.

 

Use only cable and plug components which 
comply with the appropriate fieldbus specifica-
tions.

 

Use shielded RJ45 plugs.

 

Cable length: max. 100 m between 2 subscribers.

 

PROFINET installation guidelines, see 
www.profibus.com.

 

Ethernet installation guidelines, see 
www.odva.org.

 

Installation of the communications network pur-
suant to IEC 61918.

  

 Connect the BCM 400 to the fieldbus on an 

automation system.

 

Protect the communications network against 
unauthorized access.

Commissioning

 WARNING

Risk of explosion! Do not enable the BCM and 
control unit (BCU) for operation until the parameter 
settings and wiring are correct and the faultless 
processing of all input and output signals has been 
ensured.
In the event that the bus communication is faulty or 
interrupted, or the communications data is invalid, 
or during initialization, the signals received by the 
controller are interpreted as “0”. If the control unit 
is activated using the inputs at the terminals dur-
ing this time, the normal program runs. Be sure 
to take the settings of parameters A085 to A089 
into account.

 WARNING

Danger through uncontrolled burner start.

The control signals for start and external air valve 

have an OR link between the bus and input termi-
nals. The BCU may start the burner if there is an 
active signal on the bus or terminal.

Depending on the bus module version (BCM..B2 or 
BCM..B3), fieldbus communication can be config-
ured using the engineering tool of the automation 
system or using BCSoft.

BCM..S

 can only be commissioned using BCSoft. 

Further information can be found in TI BCU 46x or 
BCU 480.

 

The BCSoft operating instructions and software 

can be downloaded from www.docuthek.com.

  

 Check the code switch settings (001 to FEF) on 

the BCM for communication between BCSoft 
and the control unit via Ethernet.

 

Each code switch setting combination may only 
exist once within the fieldbus system.

 

Each device name/network name and each IP 
address may only be allocated once within the 
fieldbus system.

 

PROFINET:

 a device within the fieldbus system 

can be identified using the subscriber flash test 
(display shows 

00

 with alternately highlighted 

segments).

 

For instructions on commissioning the control 
unit, see operating instructions “Burner control 
unit BCU 46x, 480”.

 

If the fault message 

   1 

 to 

   4  

 flashes in the 

control unit’s display, fieldbus communication 
cannot be commissioned, see also page  4 
(Assistance in the event of malfunction). The 
control unit can continue to be operated via its 
digital inputs. Be sure to take the settings of 
parameters A085 to A089 into account.

BCM..B (PROFINET)

 

All the device-specific parameters for the control 

unit (BCU) are saved in the device master data 

file (GSD): download the device master data file 
(GSD) from www.docuthek.com.

 

 Read the GSD file into the engineering tool of the 

automation system and complete the network 
configuration.

 

The steps required for this are described in the 

instructions for the engineering tool.

  

 Connect voltage to the BCU.

  

 Configure the bus communication.

 

Using the engineering tool of the automa-
tion system:

 enter the device name for the 

control unit.

 

Using BCSoft:

 enter the network name, IP ad-

dress, subnet mask and standard gateway for 
the control unit.

 

Only when the device name/network name 
has been entered, does the control unit receive 
unique identification in the PROFINET IO system.

 

On the control unit, parameter A080 must be set 
to 1 or 2 so that a device name/network name 
can be entered for the BCM, see also page 4 
(Fieldbus configuration (parameter A080)).

BCM..B (EtherNet/IP)

 

All the device-specific parameters for the con-

trol unit (BCU) are saved in the electronic data 
sheet file (EDS): download the EDS file from 
www.docuthek.com.

  

  Read the EDS file into the engineering tool of the 

automation system and complete the network 
configuration.

 

The steps required on the controller are described 

in the instructions for the engineering tool.

  

 Connect voltage to the BCU.

 4 

 Configure the bus communication.

 

 Enter the following data via the engineering tool 
of the automation system or BCSoft: network 

name, IP address, subnet mask and standard 
gateway for the control unit.

Содержание BCM 400 B2 Series

Страница 1: ...uations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 04 19 The following chapters have been changed C...

Страница 2: ...trol via bus Part designations 4 5 2 3 7 8 1 1 BCM 3 with RJ45 sockets 2 RJ45 socket port P1 for connecting to the bus communications system 3 RJ45 socket port P2 for connecting to the bus communications system 4 Green LED to indicate a connection off no connection on connection flashing data transfer 5 Yellow LED to indicate the transfer rate on 100 Mbit off 10 Mbit 7 Code switches 8 Type label M...

Страница 3: ...s may only be allocated once within the fieldbus system PROFINET a device within the fieldbus system can be identified using the subscriber flash test display shows 00 with alternately highlighted segments For instructions on commissioning the control unit see operating instructions Burner control unit BCU 46x 480 If the fault message 1 to 4 flashes in the control unit s display fieldbus communica...

Страница 4: ...et on the code switches must be identical to the address xxx entered in the automation system s network configuration After the code switch settings have been changed the control unit must be switched off and on again to enable the new address setting 5 Start the network communication The BCU powers up If the IP address is valid the program can be started Parameter A080 2 Fieldbus communication wi...

Страница 5: ...assigned in the engineering tool or replace it with an individual name e g Furnacezone1 Check whether the device name name in the network configuration is the same as the device name saved in the control unit Check the value of parameter A080 and adjust it if necessary 4 The display on the control unit blinks and indicates 4 The controller is set to Stop Start the controller E E The display on the...

Страница 6: ...ee page 5 Technical data Transport is subject to the ambient conditions de scribed Report any transport damage on the unit or packag ing without delay Check that the delivery is complete see page 2 Part designations Storage Storage temperature see page 5 Technical data Storage is subject to the ambient conditions de scribed Storage time 6 months before using for the first time If stored for longer...

Отзывы: