MPT
700
5
1.1
Version and model
•
MPT 700 with
two burner groups
per unit:
- current version: Type 2 / program version 6.0
- 8 modes of operation
- two parameter sets, switchable
- two mA inputs
- one three-point step input for multiplex operation
The MPT 700 can be adjusted to behave in the same way as a single-group unit
by setting the number of outputs for group 1 to 8 burners (parameter 15) and for
group 2 to 0 burners (parameter 16) and the setting indicator to group 1
(parameter 14).
To check the version, proceed as follows (see also section 2):
•
Set the parameter number to 0 using the right section of the keypad.
•
Press the top button on the right (+) for 5 sec.
⇒
the type and the program version number will then appear on the display.
Example:
display: 02.60
⇒
Type 2 / program version 6.0
MPT 700:
•
new model with swVcc (+12...24VDC) and common ground (GND)