Krom Schroder VAS Series Скачать руководство пользователя страница 3

GB-3

D

GB

F

NL

I

E

 

Installation position: black solenoid actuator in 
the vertical upright position or tilted up to the 
horizontal, not upside down.

 

The housing must not be in contact with masonry. 

Minimum clearance 20 mm (0.78").

 

Ensure that there is sufficient space for installa-
tion, adjustment and maintenance work. Mini-
mum clearance of 50 cm (19.7") above the black 
solenoid actuator.

 

The inlet pressure p

u

 and the outlet pressure p

d

 

can be measured using the pressure test points 
on both sides.

p

d

p

u

Strainer

 

A strainer must be fitted in the unit on the inlet 

side. If two or more gas solenoid valves are in-
stalled in line, then a strainer only needs to be 

fitted on the inlet side of the first valve.

Differential pressure orifice

 

If pressure regulator VAD/VAG/VAV 1 is retrofitted 
upstream of gas solenoid valve VAS 1, a DN 25 
differential pressure orifice with outlet opening 
d = 30 mm (1.18") must be inserted at the outlet 
of the pressure regulator.

 

 In the case of pressure regulator VAx 115 or 
VAx 120, the DN 25 differential pressure orifice 

must be ordered separately and retrofitted, Order 
No. 74922240.

 

The retaining frame must be fitted to secure the 

differential pressure orifice at the outlet of the 
regulator.

Retaining frame

 

If two controls (regulators or valves) are as-
sembled, a retaining frame with double block 
seal must be fitted, see accessories, seal set 
for sizes 1 – 3.

 

 

The seals in some gas compression fittings 

are approved for temperatures of up to 70°C 
(158°F). This temperature limit will not be ex-
ceeded if the flow through the pipe is at least 

1 m

3

/h (35.31 SCFH) of gas and the maximum 

ambient temperature is 50°C (122°F).

VAS with flanges
 1 

 Note direction of flow.

2

3

VAS without flanges
 1 

 Note direction of flow.

2

3

4

5

6

7

 

O-ring and strainer (Fig. 

 4 

) must be fitted.

2

3

4

5

6

7

Содержание VAS Series

Страница 1: ...Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 17 The following c...

Страница 2: ...ve is not damaged during installation and operation Sealing material and dirt e g thread cuttings must not be allowed to get into the valve hous ing A filter must be installed upstream of every sys te...

Страница 3: ...lenoid valve VAS 1 a DN 25 differential pressure orifice with outlet opening d 30 mm 1 18 must be inserted at the outlet of the pressure regulator In the case of pressure regulator VAx 115 or VAx 120...

Страница 4: ...ing Type 2 the en closure openings shall be closed with fittings rated UL Type 2 3 3R 3RX 3S 3SX 3X 4X 5 6 6P 12 12K or 13 Gas solenoid valves shall be protected by a branch circuit protective device...

Страница 5: ...re is a risk of interference between valve voltage and proof of closure switch voltage To make wiring easier the connection terminal for the proof of closure switch can be removed 1 3 2 LV1 N 1 3 2 LV...

Страница 6: ...if the adjusting screw is overturned Setting the start gas rate on VAS L VCS L The start gas rate can be set by turning the damping unit a maximum of 5 turns There must be a period of 20 seconds betwe...

Страница 7: ...VAS 2 3 use the small seal from the actuator adapter set and only one of the large seals VAS 1 3 10 11 Slide seal under the second groove 12 Position new actuator 13 Follow the reverse procedure when...

Страница 8: ...4 5 3 10 9 Maintenance CAUTION In order to ensure smooth operation check the tightness and function of the VAS Once per year twice per year in the case of biogas check for internal and external tight...

Страница 9: ...ion from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Bypass pilot gas valves 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Pr...

Страница 10: ...10 mm 0 39 at the outlet of the main valve if the bypass valve s outlet flange is designed as a blind flange For the pilot gas valve insert sealing plug F at the outlet of the main valve if the pilot...

Страница 11: ...s piloto ppna bypass eller t ndgasven tilen pne bypass eller tenn gassventilen Otev t obto kov ventil nebo zapalovac plynov ventil Otworzy zaw r obej ciowy lub zaw r gazu zap onowego Tightness control...

Страница 12: ...nnect the system from the electrical power supply Shut off the gas supply 16 5 4 3 8 7 6 9 10 13 12 11 15 14 In both connection boxes push through the knock out for the cable gland set then remove the...

Страница 13: ...AMSL Ambient temperature 20 to 60 C 4 to 140 F no condensation permitted Long term use in the upper ambient temperature range accelerates the ageing of the elastomer ma terials and reduces the servic...

Страница 14: ...3 A VAS G 12 30 V DC 2 mA 0 1 A Switching frequency of proof of closure switch max 5 x per minute Switching current A Switching cycles cos 1 cos 0 6 0 1 500 000 500 000 0 5 300 000 250 000 1 200 000 1...

Страница 15: ...in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby decl...

Страница 16: ...earch Class 7400 and 7411 Safety overpressure slam shut valves Designed for applications pursuant to NFPA 85 and NFPA 86 ANSI CSA approved Canadian Standards Association ANSI Z21 21 and CSA 6 5 UL lis...