Checking the usage

Intended use

Gas solenoid valves VAS for safeguarding gas or air 
on various appliances. Double solenoid valves VCS 
are combinations of two gas solenoid valves VAS.

This function is only guaranteed when used within the 

specified limits – see page 13 (Technical data). Any 
other use is considered as non-compliant.

Type code

Code

 Description

VAS

Gas solenoid valve

1 – 

Sizes

T

T-product

10 – 65

Inlet and outlet flange nominal size

N

Rp internal thread 

NPT internal thread (ANSI/ASME)

/N 

/L

Quick opening, quick closing 

Slow opening, quick closing

 

Y

Mains voltage: 

230 V AC, 50/60 Hz 

120 V AC, 50/60 Hz 

24 V DC 

100 V AC, 50/60 Hz 

200 V AC, 50/60 Hz

 

G

With visual position indicator 

and proof of closure switch 

and proof of closure switch for 24 V 

 

L

Viewing side (in flow direction): 

from the right 

from the left

 

 

Electrical connection: 

plug with socket 

plug without socket 

M20 cable gland

Part designations

VAS..S, VAS..G

VAS

1

2

3

4

5
6
7

1

Solenoid actuator

Flow body

Connection box

4

Connection flange

5

Proof of closure switch

6

Connection parts

7

Sealing plug

Mains voltage, electrical power consumption, ambi-
ent temperature, enclosure, inlet pressure and instal-
lation position: see type label.

Elster GmbH

Osnabrück, Made in Germany

VAS ...

 

.XXXX

Installation

 CAUTION

Please observe the following to ensure that the gas 
solenoid valve is not damaged during installation 
and operation:

–   Sealing material and dirt, e.g. thread cuttings, 

must not be allowed to get into the valve hous-
ing.

–   A filter must be installed upstream of every sys-

tem.

–   It is not permitted to install gas solenoid 

valve  VAS downstream of flow rate regula-
tor VAH/VRH and upstream of fine-adjusting 
valve VMV. The VAS would no longer be able 
to perform its function as a second safety valve 

if installed in the above-mentioned position.

–   Dropping the device can cause permanent 

 damage. In this event, replace the entire device 
and associated modules before use.

–   If more than three valVario controls are installed 

in line, the controls must be supported.

–   Do not clamp the unit in a vice. Only secure the 

flange by holding the octagon with a suitable 

spanner. Risk of external leakage.

–    Solenoid valves with overtravel switch and visual 

position indicator VAS..SR/SL: actuator cannot 
be rotated.

–    In the case of double solenoid valves, the posi-

tion of the connection box can only be changed 
by removing the actuator and reinstalling it ro-
tated by 90° or 180°.

 

When joining two valves, determine the posi-
tion of the connection boxes, push through the 

knock-outs in the connection boxes and install 
a cable gland set before installation in the pipe-
work, see accessories, cable gland set for double 
solenoid valves.

 

Install the unit in the pipe free of mechanical 
stress.

 

For retrofitting a second gas solenoid valve, use 
the double block seal instead of O-rings. The 
double block seal is supplied with the seal set, 
see accessories, seal set for sizes 1 – 3.

Содержание VAS Series

Страница 1: ...Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 17 The following c...

Страница 2: ...ve is not damaged during installation and operation Sealing material and dirt e g thread cuttings must not be allowed to get into the valve hous ing A filter must be installed upstream of every sys te...

Страница 3: ...lenoid valve VAS 1 a DN 25 differential pressure orifice with outlet opening d 30 mm 1 18 must be inserted at the outlet of the pressure regulator In the case of pressure regulator VAx 115 or VAx 120...

Страница 4: ...ing Type 2 the en closure openings shall be closed with fittings rated UL Type 2 3 3R 3RX 3S 3SX 3X 4X 5 6 6P 12 12K or 13 Gas solenoid valves shall be protected by a branch circuit protective device...

Страница 5: ...re is a risk of interference between valve voltage and proof of closure switch voltage To make wiring easier the connection terminal for the proof of closure switch can be removed 1 3 2 LV1 N 1 3 2 LV...

Страница 6: ...if the adjusting screw is overturned Setting the start gas rate on VAS L VCS L The start gas rate can be set by turning the damping unit a maximum of 5 turns There must be a period of 20 seconds betwe...

Страница 7: ...VAS 2 3 use the small seal from the actuator adapter set and only one of the large seals VAS 1 3 10 11 Slide seal under the second groove 12 Position new actuator 13 Follow the reverse procedure when...

Страница 8: ...4 5 3 10 9 Maintenance CAUTION In order to ensure smooth operation check the tightness and function of the VAS Once per year twice per year in the case of biogas check for internal and external tight...

Страница 9: ...ion from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Bypass pilot gas valves 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Pr...

Страница 10: ...10 mm 0 39 at the outlet of the main valve if the bypass valve s outlet flange is designed as a blind flange For the pilot gas valve insert sealing plug F at the outlet of the main valve if the pilot...

Страница 11: ...s piloto ppna bypass eller t ndgasven tilen pne bypass eller tenn gassventilen Otev t obto kov ventil nebo zapalovac plynov ventil Otworzy zaw r obej ciowy lub zaw r gazu zap onowego Tightness control...

Страница 12: ...nnect the system from the electrical power supply Shut off the gas supply 16 5 4 3 8 7 6 9 10 13 12 11 15 14 In both connection boxes push through the knock out for the cable gland set then remove the...

Страница 13: ...AMSL Ambient temperature 20 to 60 C 4 to 140 F no condensation permitted Long term use in the upper ambient temperature range accelerates the ageing of the elastomer ma terials and reduces the servic...

Страница 14: ...3 A VAS G 12 30 V DC 2 mA 0 1 A Switching frequency of proof of closure switch max 5 x per minute Switching current A Switching cycles cos 1 cos 0 6 0 1 500 000 500 000 0 5 300 000 250 000 1 200 000 1...

Страница 15: ...in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby decl...

Страница 16: ...earch Class 7400 and 7411 Safety overpressure slam shut valves Designed for applications pursuant to NFPA 85 and NFPA 86 ANSI CSA approved Canadian Standards Association ANSI Z21 21 and CSA 6 5 UL lis...