6.3 setting the damping speed on the VAA../L 

 

The opening speed can be influenced by turning 

the nozzle screw on the damping unit.

 CAUtIon

Attention! To avoid leakage, please observe the 

following:

 

– If the nozzle screw is turned by more than 

1 turn, the damping unit will leak and will have 
to be replaced.

 

Turn the nozzle screw a maximum of 1/2 a turn in 

the appropriate direction. 

-

+

7 RePLACInG tHe ACtUAtoR

 

The actuator adapter set for the new actuator must 

be ordered separately.

VAx 2 – 3,

VCx 2 – 3

VAx 1,

VCx 1

VAx 1, VCx 1: Order No. 74924468,  
VAx 2–3, VCx 2–3: Order No. 74924469. 

7.1 Removing the actuator
VAA without damping unit 

 1 

Disconnect the system from the electrical power 

supply.

 2 

Close the gas supply.

 3 

 

 4 

 

 5 

 

 6 

 

 7 

 

 8 

 

Remove the M20 cable gland or other type of 
connection.

VAA without proof of closure switch

 

 a 

 

 b 

 

 c 

VAA with proof of closure switch

 

 a 

 

 b 

 

 c 

 

 d 

 

 e 

VAA with damping unit 

 1 

Disconnect the system from the electrical power 

supply.

 2 

Close the gas supply.

 

Remove the M20 cable gland or other type of 
connection.

 

Loosen the setscrews, but do not unscrew com-
pletely (M3 = 1.5  mm hexagon socket, M5 = 

2.5 mm hexagon socket).

 3 

M3

 

 4 

 

 5 

M5

 

 6 

1.

2.

 

 7 

 

 8 

 

 9 

 

 10 

 

 11 

7.2 Fitting the new actuator

 

The seals of the actuator adapter set are covered 

with a non-stick coating. No additional grease is 
required.

 

Depending on the construction stage of the unit, there 
are two different methods for replacing the actuator:  
If the unit concerned has no O-ring in this place 
(arrow), replace the actuator as described here. 
Otherwise, go to the next note. 

 1 
 2 

Insert seals.

 3 

Position of the metal ring can be selected.

Содержание valVario VAA 1

Страница 1: ...This unit must be installed and commissioned in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c...

Страница 2: ...ent temperature enclosure inlet pressure and installation position see type label Elster GmbH Osnabr ck Germany Vxx XXXX 3 INSTALLATION CAUTION Incorrect installation Please observe the following to e...

Страница 3: ...ended tightening torques for the connection parts See page 10 12 Technical data f g 4 WIRING WARNING Risk of injury Please observe the following to ensure that no damage occurs Electric shocks can be...

Страница 4: ...on switch can be removed 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 1 3 2 LV1 N 1 COM 2 Valve open Valve closed 3 When installing two plugs on VAA a with position switch label the sockets and plugs...

Страница 5: ...adjusted for maximum flow rate Q The markings on the cover cap can be used for coarse adjustment of the flow rate The cover cap can be rotated without changing the current flow rate Allen key 2 5 mm D...

Страница 6: ...ly 2 Close the gas supply 3 4 5 6 7 8 Remove the M20 cable gland or other type of connection VAA without proof of closure switch a b c VAA with proof of closure switch a b c d e VAA with damping unit...

Страница 7: ...nit 1 2 3 4 5 6 7 Open the gas solenoid valve and the gas supply VAA with proof of closure switch Depending on the design of the proof of closure switch one of the two enclosed seals must be inserted...

Страница 8: ...5 13 Switch on the solenoid actuator so that the guide pin becomes visible 14 15 Switch off the solenoid actuator The damping unit is lowered 16 17 M3 18 Open the air supply and switch on the power su...

Страница 9: ...on to the PE wire see page 3 4 Wiring 11 ACCESSORIES 11 1 Pressure switch for gas DG VC The pressure switch for gas monitors the inlet pres sure pu and the outlet pressure pd Monitoring the inlet pres...

Страница 10: ...essure cleaner and or cleaning products 12 2 Mechanical data Gas types clean air The air must be clean and dry in all temperature conditions and must not contain condensate Medium temperature ambient...

Страница 11: ...s been reached safety relevant products must be replaced Designed lifetime based on date of manufacture in accordance with EN 13611 EN 161 for VAA Type Designed lifetime Switching cycles Time years VA...

Страница 12: ...of the Disclosure Table China RoHS2 see certificates at www docuthek com 16 DISPOSAL Devices with electronic components WEEE Directive 2012 19 EU Waste Electrical and Electronic Equipment Directive A...

Отзывы: