PFU 780 · Edition 02.12
40
4 .7 .5 Air valve opens in the case of external activation (even
during start-up)
A2
00 A0 00 A0
t
SA2
A8
A7
A4
t
t
FS2
A6
t
SA1
t
Z
t
FS1
A3
A
10a
22e
26a
16c
18e
2c–4c
18a
14a
88
10e
26e
30a
28c
2e–4e
6a–6e
V1
1
V2
2
ϑ
1
ϑ
2
2
1
VAG
PFU 780..L
A
P
L1
1
2
ϑ
VAS
TZI
2
1
UV
VAS 1
Parameter 30 = 0:
The air valve opens if it is activated externally via input 10a.
Parameter 31 = 1:
The air valve can be activated even during start-up.
These settings may be selected only if the burner can start
with full air capacity.
The air valve can be activated externally via input 10a for cool-
ing the burner in the start-up position/standby.
Parameters > Air valve control PFU . .L