background image

DK

S

N

P

GR

 www.docuthek.com

D

GB

F

NL

I

E

TR

CZ

PL

RUS

H

© 2012 Elster GmbH

Safety

Please read and keep in a safe place

 Please read through these instructions 

carefully before installing or operating. Following the 
installation, pass the instructions on to the opera-
tor. This unit must be installed and commissioned 
in accordance with the regulations and standards 
in force. These  instructions can also be found at 
www.docuthek.com.

Explanation of symbols

 • 

,   ,   ,   

... = Action

 

= Instruction

Liability

We will not be held liable for damages resulting 
from non-observance of the instructions and non-
compliant use.

Safety instructions

Information that is relevant for safety is indicated in 
the instructions as follows:

 DANGER

Indicates potentially fatal situations.

 WARNING

Indicates possible danger to life and limb.

 CAUTION

Indicates possible material damage.

All interventions may only be carried out by qualified 
gas technicians. Electrical interventions may only be 
carried out by qualified electricians.

Conversion, spare parts

All technical changes are prohibited. Only use OEM 
spare parts.

Transport

On receipt of the product, check that the delivery is 
complete (see Part designations). Report any trans-
port damage immediately. 

Storage

Store the product in a dry place. Ambient tempera-
ture: see Technical data.

Contents

Operating instructions

Translation from the German

D

GB

F

NL

I

E

GB-1

0500 · Edition 0.

Safety

Contents

Safety shut-off valve JSAV 5 – 40

Safety shut-off valve JSAV 5 – 40  . . . . . . . . . 
Contents  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Checking the usage . . . . . . . . . . . . . . . . . . . . . 

Type code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Part designations . . . . . . . . . . . . . . . . . . . . . . . . 2

Type label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
Connecting the impulse line . . . . . . . . . . . . . . 

Tightness test . . . . . . . . . . . . . . . . . . . . . . . . . . 

Checking the function . . . . . . . . . . . . . . . . . . . 4

Checking the trip pressure . . . . . . . . . . . . . . . . . 4
Checking the tightness of the valve disc. . . . . . . 4

Setting the trip pressure  . . . . . . . . . . . . . . . . . 4
Replacing the spring  . . . . . . . . . . . . . . . . . . . . 4
Resetting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Replacing the measuring unit. . . . . . . . . . . . . 5
Replacing the valve disc  . . . . . . . . . . . . . . . . . 6
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . 7

Designed lifetime  . . . . . . . . . . . . . . . . . . . . . . . . 8

Declaration of conformity . . . . . . . . . . . . . . . . 8
Contact  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Содержание JSAV 25

Страница 1: ...only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM sp...

Страница 2: ...com D 49018 Osnabr ck Germany JSAV pu 4 bar pdu 10 mbar 8 16 pdo 140 mbar 10 210 T 20 C 60 C Klasse A IS CE 0085AS0202 www kromschroeder com D 49018 Osnabr ck Germany Installation CAUTION Please obser...

Страница 3: ...on nut and compression fitting onto the impulse line On the JSAV T remove the blind plug and con nect an NPT 1 8 impulse line 5 Install the impulse line and seal with approved sealing material Ensure...

Страница 4: ...pdo according to the outlet pressure pd of the pressure regulator 20 0 40 60 80 100 140 180 220 260 300 340 50 100 150 200 250 300 350 400 450 500 pd mbar p do mbar VSBV JSAV 2 Remove the breather scr...

Страница 5: ...pressures pdo and pdu on the adhesive label s 10 Screw in the breather screw plug 11 Check tightness and function see page 3 Tightness test and page 4 Checking the function Resetting Ensure that the...

Страница 6: ...st and page 4 Checking the function Replacing the valve disc The valve disc has to be replaced if the JSAV is leaking We recommend cleaning the O ring seats and lightly greasing the O rings with Kl be...

Страница 7: ...c and replace if necessary Selecting spare parts see free PartDetective DVD www kromschroeder com Products DVD PartDetective D GB Replacing spare parts see page 5 Replacing the measuring unit see page...

Страница 8: ...d functions must be checked in accordance with the section entitled Maintenance If the product passes the aforementioned function tests you can continue to use it until the next sched uled maintenance...