Maintenance

 CAUTION

In order to ensure smooth operation: clean or re-
place the filter pad of the GFK every year, or every 
six months if operated with biologically produced 
methane.
When cleaning or replacing the filter pad, no dirt 
may contaminate the clean gas circuit.

 

The filter pad should be changed at a pressure 

gradient ≥ 20 mbar (8 "WC).

 

Pressure test points on the cover:

 

GFK 15 to 100:

 

Inlet side: Rp 1/8 pressure test nipple,

 

Outlet side: Rp 1/8 pressure test nipple.

 

GFK 125 to 250:

 

Inlet side: Rp 1/8 plug,

 

Outlet side: Rp 1/8 plug.

 

GFK 15T to 100T:

 

Inlet side: Rp 1/8 plug,

 

Outlet side: Rp 1/8 plug.

Recommended ∆

p

 max. = 20 mbar

Cleaning or replacing the filter pad
 1 

 Shut off the gas supply.

5

2

3

4

8

6

7

10

11

9

Clean or 
replace the 
filter pad.

Fit the filter 
pad into the 
groove in the 
cover. 

 

Tighten screws in a crosswise fashion and pay 

attention to the torque, see table:

Type

Torque [Nm]

GFK 15

5

GFK 20

5

GFK 25

8

GFK 32

8

GFK 40

8

GFK 50

8

GFK 65

8

GFK 80

20

GFK 100

20

GFK 125

60

GFK 150

60

GFK 200

80

GFK 250

80

Checking tightness and function

 

When replacing the filter pad, the gas-filled space 

in the GFK is opened. Therefore, check for tight-
ness once the filter pad has been reinstalled.

 1 

 To be able to check the tightness, shut off the 

downstream pipeline close to the gas filter.

 

≤ 

1,2 x p

u max

N

2

14

13

 15 

 Tightness OK: open the pipeline.

Technical data

Gas type: natural gas, town gas, LPG (gaseous), 
biologically produced methane and air.
Max. inlet pressure p

u max

GFK 15 to 250: 1 bar (14.5 psig), 
GFK 15R to 65R: 4 bar (60 psig), 
GFK 15TN to 100TN: 4 bar (60 psig), 
GFK 40F to 100F: 6 bar (87 psig).
Storage temperature: -15 to +60°C (5 to 140°F). 

Ambient temperature: -15 to +80°C (5 to 176°F). 

Continuous operation at high temperatures ac-
celerates the ageing of elastomer materials.  
Version to DIN 3386.
Housing material:
GFK 15 to 100: AlSi. 
GFK 125 to 250: sheet steel.
Connection: 
GFK..R: Rp internal thread connection to ISO 7-1. 
GFK..F: flanged connection to ISO 7005, PN 16. 
GFK..N: NPT internal thread. 
GFK..A: ANSI 150 flanged connection.
Filter pad: polypropylene fleece (standard 50 μm).

Содержание GFK Series

Страница 1: ...nstructions as follows DANGER Indicates potentially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Change...

Страница 2: ...outlet Part designations GFK F GFK R 1 1 3 2 2 1 Housing cover 2 Lower housing section 3 Pressure test point Type label Max inlet pressure see type label D 49018 Osnabrück Germany GFK pu max Installation CAUTION Dropping the device can cause permanent dam age In this event replace the entire device and associated modules before use Installation position any in horizontal or verti cal pipework reco...

Страница 3: ...FK 40 8 GFK 50 8 GFK 65 8 GFK 80 20 GFK 100 20 GFK 125 60 GFK 150 60 GFK 200 80 GFK 250 80 Checking tightness and function When replacing the filter pad the gas filled space in the GFK is opened Therefore check for tight ness once the filter pad has been reinstalled 12 To be able to check the tightness shut off the downstream pipeline close to the gas filter 1 2 x pu max N2 14 13 15 Tightness OK o...

Страница 4: ...xtra storage time Packaging The packaging material is to be disposed of in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare that the prod uct GFK marked with product ID No 0063AU1408 complies with the essential requirements of the fol lowing Directi...

Отзывы: