GB-28
D
GB
F
NL
I
E
Interface parameters
▷
Interface parameters I040 to I099 are set at the
factory and normally do not need to be adjusted.
CAUTION
Changing the default settings of the interface pa-
rameters will change the functions of the inputs
at terminals 1 to 41 and terminals 85 to 90, see
page 7 (Connection diagram).
Param-
eter No.
Parameter name
Parameter value
I004
Flame control
0
= Ionization
1
= UVS
2
= UVC
3
= Ionization 1 and UVS 2
4
= Ionization 1 and UVC 2
5
= UVS 1 and ionization 2
6
= UVC 1 and UVC 2
7
= UVC 1 and ionization 2
8
= UVC 1 and UVS 2
I020
Air actuator
1
= IC 20
2
= IC 40
3
= RBW
4
= Frequency converter
5
= Air valve
I040
Function of terminal 64
0
= Off
1
= Controller enable
2
= V5
3
= Bus output 1
I050
Contact 80, 81/82 function
0
= Off
1
= Ready signal
2
= Air signal
3
= Purge signal
4
= Cooling air valve
5
= Flue gas valve
6
= Fault signal
7
= Burner 1 operating signal
8
= Burner 2 operating signal
I051
Contact 90, 91/92 function
▷
See parameter
I050
for parameter values
I052
Function of contact 95/96
▷
See parameter
I050
for parameter values
I053
Function of contact 95/97
▷
See parameter
I050
for parameter values
I054
Contact 85/86, 87 function
▷
See parameter
I050
for parameter values
Param-
eter No.
Parameter name
Parameter value
I061
Function of input 1
0
= Off
1
= Sensor 1
2
= Sensor 2
3
= Sensor 3
4
= Safety interlocks
5
= Air
6
= Cooling air
7
= Air actuator R1
8
= Air actuator R2
9
= Start 1
10
= Start 2
11
= Reset
12
= Purge
13
= LDS
14
= HT
15
= Flame mode
16
= Flameless operation
17
= menox
19
= Auxiliary gas
I062
Function of input 2
▷
See parameter
I061
for parameter values
I063
Function of input 3
▷
See parameter
I061
for parameter values
I064
Function of input 4
▷
See parameter
I061
for parameter values
I065
Function of input 5
▷
See parameter
I061
for parameter values
I066
Function of input 6
▷
See parameter
I061
for parameter values
I067
Function of input 7
▷
See parameter
I061
for parameter values
I068
Function of input 35
▷
See parameter
I061
for parameter values
I069
Function of input 36
▷
See parameter
I061
for parameter values
I070
Function of input 37
▷
See parameter
I061
for parameter values
I071
Function of input 38
▷
See parameter
I061
for parameter values
I072
Function of input 39
▷
See parameter
I061
for parameter values
I073
Function of input 40
▷
See parameter
I061
for parameter values
I074
Function of input 41
▷
See parameter
I061
for parameter values