GB-26
D
GB
F
NL
I
E
Param-
eter No.
Parameter name
Parameter value
A043
Over-run
0
= Off
1
= Post-ventilation
2
= Low fire; actuator feedback
3
= Low fire; time-bound
A044
Controller enable signal delay time t
RF
0 – 250
= Time in seconds
A048
Air actuator control
0
= Opens on external activation
1
= Opens with gas stage 1
2
= Opens with gas stage 2
3
= Controller enable op./standby
4
= Opens with V4 burner 1
5
= Controller enable following operating
signal
6
= Opens with gas stage 3
A049
Air actuator can be activated externally on
start-up
0
= Cannot be activated
1
= Can be activated externally
A050
Air actuator in the event of fault
0
= Cannot be activated
1
= Can be activated externally
A051
Valve proving system
0
= Off
1
= Tightness test before start-up
2
= Tightness test after shut-down
3
= Tightness test before start-up and after
shut-down
4
= POC function
A052
Relief valve (VPS)
0
= V0
1
= V1
2
= V2
3
= V3
4
= V4
5
= V5
A056
Measurement time Vp1
0 – 3600
= Time in seconds
A059
Valve opening time 1 t
L1
2 – 25
= Time in seconds
A060
POC test period
0 – 250
= Time in seconds
A061
Minimum operating time t
B
0 – 6000
= Time in seconds
A062
Minimum pause time t
BP
0 – 3600
= Time in seconds
A064
Flameless operation
0
= Upon next burner start
1
= Immediate burner start
2
= Immediate switchover
A067
Operating time in Manual mode
0
= Unlimited
1
= 5 minutes
A074
Combustion mode
0
= Flame mode
1
= menox
2
= HT without ignition
3
= HT without burner 1 start
4
= FLOX
Param-
eter No.
Parameter name
Parameter value
A075
Air actuator (bus)
0
= Off
1
= MAX to MIN
2
= MAX to LOW FIRE
3
= MAX to IGNITION
4
= MAX to MIN; red. purge flow
5
= MAX to IGN; red. purge flow
A076
Function of V5
0
= Off
1
= Flame mode
2
= Flameless operation
3
= Operation
A077
Auxiliary gas function
0
= Off
1
= Flame mode
2
= Flameless operation
3
= Operation
A078
Burner application
0
= Burner 1
1
= Burner 1 with pilot gas
2
= Burner 1 & burner 2
3
= Br. 1 & Br. 2 with pilot gas
4
= Two-stage burner 1
5
= Br. 1 & two-stage br. 2
11
= menox 1/0 and burner 1/0
12
= menox 1/0 and burner L/H/O
13
= menox 1/0 with 2 gas paths
14
= menox L/H/O with 2 gas paths
21
= CBFF flame
22
= CBFF flame Flox
A079
Gas pilot
0
= With shut-down
1
= In continuous operation
2
= With shut-down & restart
A080
Fieldbus communication
0
= Off
1
= With address check
2
= No address check
A081
K” Safety Link
0
= Off
1
= On
A085
Safety interlocks (bus)
0
= Off
1
= Via FS bus
2
= Via terminal
3
= Via NFS bus
4
= Via FS bus or terminal
5
= Via FS bus and terminal
A086
FLOX800 (bus)
0
= Off
1
= Via FS bus
2
= Via terminal
3
= Via NFS bus
4
= Via FS bus or terminal
5
= Via FS bus and terminal