background image

 OPERATION 

5

35

TT 51 SERIES

www.krohne.com

08/2015 - 4000754203 - MA TT 51 R03 en

5.5  Diagnostic information according to NAMUR NE 107

Diagnostic information about the connected sensor/sensors is available in the configuration 
software ConSoft.

The HART

®

 diagnostic messages are generated in accordance with NAMUR NE 107 for:

Sensor break (failure / sensor wire break on Ch1 or Ch2)

Sensor short-circuit (failure / sensor wire short-circuit on Ch1 or Ch2)

Sensor low isolation (failure / low internal isolation in sensor on Ch1 or Ch2)

Sensor drift (failure / sensor drift between Ch1 and Ch2)

Sensor backup, automatic switchover from defective sensor (maintenance required / change 
the sensor on Ch1 or Ch2)

Transmitter error (failure/transmitter error, non-correctable in the transmitter)

For complete information about all diagnostic information available from the transmitters, refer 
to the following tables.

Explanations acc. to NE 107

C: check function

S: not within specification

M: maintenance required

F: failure

Messages in AMS, PDM and FC 375 / FC 475 device 
diagnostic

Actions

Standard

NE 107
Signal 
[12]

Error message

Error correction

Transmitter

C

Primary variable out of 

limits

Check the limits for connected sensor. Replace the sensor 

allocated to the primary variable.

Transmitter

C

Non-primary variable out 

of limits

Check the limits for connected sensor. Replace the sensor 

allocated to the non-primary variable.

Transmitter

C

Primary variable analogue 

output saturated

Check the limits for connected sensor. Ambient 

temperature is higher then stated limits for sensor, which 

is allocated to the primary variable analogue output. 

Replace the sensor allocated to the primary variable 

analogue output.

Transmitter

I

Primary variable analogue 

output fixed

Transmitter in Multi-Drop mode or loop test.

Transmitter

C

More status variable

Check device specific errors for more information.

Transmitter

I

Cold start

Transmitter is in cold start mode.

Transmitter

I

Configuration changed

Information for other softwares.

Transmitter

C

Field device malfunction

Make a self test to find out more. Check even device 

specific diagnostic. If the error remains replace the device.

Extended device status

Extended device status

Extended device status

Extended device status

Transmitter

M

Maintenance required

Check device specific diagnostic for more information 

about sensors and transmitter.

Transmitter

M

Device variable alert

Check device specific diagnostic for more information 

about sensors and transmitter.

MA_OPTITEMP_TT_51_en_150828_4000754203_R03.book  Page 35  Friday, August 28, 2015  10:54 AM

Содержание TT 51 Series

Страница 1: ...T 51 SERIES TT 51 SERIES Handbook Handbook Handbook Handbook KROHNE 08 2015 4000754203 MA TT 51 R03 en The documentation is only complete when used in combination with the relevant documentation for t...

Страница 2: ...uthorisation of KROHNE Messtechnik GmbH Subject to change without notice 2 TT 51 SERIES www krohne com 08 2015 4000754203 MA TT 51 R03 en Copyright 2015 by KROHNE Messtechnik GmbH Ludwig Krohne Str 5...

Страница 3: ...n installation 14 3 2 In head transmitter 14 3 3 Rail mount transmitter 15 4 Electrical connections 16 4 1 Safety instructions 16 4 2 Electrical connections of in head transmitter 16 4 3 Connection di...

Страница 4: ...Availability of services 38 6 3 Returning the device to the manufacturer 38 6 3 1 General information 38 6 3 2 Form for copying to accompany a returned device 39 6 4 Disposal 39 7 Technical data 40 7...

Страница 5: ...mpatible 2 wire rail mount transmitter for temperature resistance or voltage measurements in an industrial environment The TT 51 R is optionally available in an intrinsically safe version for use in z...

Страница 6: ...plying the CE marking 1 2 2 Ex approvals TT 51 C intrinsically safe TT 51 R intrinsically safe 1 2 3 SIL certification Compliance functional safety acc to IEC 61508 part 1 to 3 Safety Integrity Level...

Страница 7: ...e version can be found on a small label on the product Legend Hardware hardware version IPM input module software release OPM output module software release ConSoft configuration software release Manu...

Страница 8: ...il may involve gaps in security It is not possible to protect such data completely against access by third parties We hereby expressly prohibit the use of the contact data published as part of our dut...

Страница 9: ...the device it is essential that you read the information in this document and observe applicable national standards safety requirements and accident prevention regulations If this document is not in...

Страница 10: ...al disregard of this warning can lead to serious health problems and even death There is also the risk of seriously damaging the device or parts of the operator s plant WARNING Disregarding this safet...

Страница 11: ...tallation on a rail according to EN 60715 DIN 50022 Following Ex approvals for the transmitter are available Standard version without any Ex approval Intrinsically safe version TT 51 C for use in area...

Страница 12: ...nd nameplate 1 Product name 2 CE marking EC conformity 3 Technical data 4 Part number serial number yyww year and week of manufacturing and batch number 5 Printable field sensor configuration 6 Manufa...

Страница 13: ...nsor configuration 5 Technical data 6 Electrical data for output 7 CE marking EC conformity and electronic electric device waste marking 4001027302 Nyyww xxxxxx PO ZZZZZZZZZ www krohne com TT 51 R KIW...

Страница 14: ...have all the elements given in the order INFORMATION Look at the device nameplate to ensure that the device is delivered according to your order Check for the correct supply voltage printed on the nam...

Страница 15: ...egory For detailed information refer to Ex data of the ambient temperature The process temperature is also transferred to the transmitter housing via the thermowell If the process temperature is close...

Страница 16: ...in potentially hazardous area zone 1 and 2 and the input may be connected to temperature sensors installed in zone 0 The intrinsically safe versions must be supplied by an intrinsically safe power su...

Страница 17: ...onnection RTD redundant sensor elements RTD redundant sensor elements RTD redundant sensor elements RTD redundant sensor elements 2 x 2 wire connection 2 x 2 wire connection 2 x 2 wire connection 2 x...

Страница 18: ...ave an output load of at least 250 Figure 4 1 Connection diagram 1 Voltage supply 10 36 VDC terminals 6 7 2 Modem 3 Input 4 Output 5 SmartSense temperature sensor 6 Thermocouple 7 Pt100 3 wire connect...

Страница 19: ...oad or parallel to the output of the transmitter DANGER The transmitter may be operated in areas with potentially explosive atmospheres if the voltage supply is ensured by means of an associated appar...

Страница 20: ...t1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 4 wire connection Ch1 4 wire connection Ch1 4 wire connection Ch1 4 wire connection Ch1 RTD redundant sensor elements 2 x RTD redundant sensor elements 2...

Страница 21: ...wire connection on Dual resistance 2 wire connection on Dual resistance 2 wire connection on Ch 1 and Ch 2 Ch 1 and Ch 2 Ch 1 and Ch 2 Ch 1 and Ch 2 Dual resistance 3 wire connection on Dual resistanc...

Страница 22: ...e screen s Thermocouple Thermocouple Thermocouple Thermocouple Thermocouple redundant sensor elements Thermocouple redundant sensor elements Thermocouple redundant sensor elements Thermocouple redunda...

Страница 23: ...transmitter Figure 4 3 Connection diagram 1 Input 2 Modem 3 RLoad R 250 4 Voltage supply 10 36 VDC 5 Test connection Ri 10 mA INFORMATION The HART modem is connected parallel to the output load or pa...

Страница 24: ...pacitance Number which is multiple of 5000 pF present in the device Figure 4 4 Connection diagram 1 Input intrinsically safe 2 Classified hazardous area potentially explosive area e g zone 0 1 or 2 3...

Страница 25: ...ad resistance incl the resistance of any Zener barrier cable resistsance C cable capacitance pF m or pF ft Cn number of transmitters in the loop Conductors Resistance km both conductors in series Area...

Страница 26: ...T communication with this transmitter the loop resistance must be at least 250 If the USB interface configuration modem is connected to the transmitter then the HART communication is disconnected 1 Pr...

Страница 27: ...f the devices must be passive Burst mode is not supported 1 Primary master 2 HART modem 3 HART signal 4 Other HART devices or this transmitter refer also to 7 5 Terminal 7 6 Terminal 6 7 Device with a...

Страница 28: ...sensor 1 RTD Pt100 0 003850 Number of wires 4 PV Lower range value 0 PV Upper range value 100 Digital units C Damping value 4 Line frequency 50 60 Hz Isolation resistance monitoring Off Sensor break...

Страница 29: ...rt on the PC for more information see the user instructions for ConSoft and USB Interface 2 A hand held communicator secondary master such as the field communicators FC 375 FC 475 Emerson 3 EDD enable...

Страница 30: ...er version 3 Is a ConSoft version 1 2 0 0 or higher installed on your PC 3a No 3b Yes 4 Download the current ConSoft version from our website and install it on your PC 5 Download the current software...

Страница 31: ...Connection during configuration of in head transmitter a PC configuration kit b PC software ConSoft 1 Input intrinsically safe 2 RLoad intrinsically safe 3 Output voltage supply intrinsically safe ter...

Страница 32: ...n to USB interface and a PC software ConSoft is not permitted if Ex version is placed in the classified haz ardous area potentially explosive area 6 Connection to the voltage supply during configurati...

Страница 33: ...in head transmitter intrinsically safe on page 19 and refer to Connection diagram of rail mount transmitter intrinsically safe on page 24 5 3 3 Device management software The transmitter can be config...

Страница 34: ...ic Root Menu and the Device Root Menu for online access to the device Furthermore it supports the Offline Root Menu for offline configuration 5 3 4 Configuration with PACTware PACTware is a DTM FDT en...

Страница 35: ...nnected sensor Replace the sensor allocated to the primary variable Transmitter C Non primary variable out of limits Check the limits for connected sensor Replace the sensor allocated to the non prima...

Страница 36: ...r remains replace the sensor connected to channel 1 Transmitter F Sensor low isolation channel 2 To low isolation in the sensor Check the sensor by measuring resistance between the wires If error rema...

Страница 37: ...uration TT 51 C non SIL TT 51 C SIL SIL mode on SIL mode off Error short circuit Off upscale downscale Upscale downscale Off upscale downscale Error wire broken Off upscale downscale Upscale downscale...

Страница 38: ...roblems INFORMATION For more precise information please contact your local sales office CAUTION Should you nevertheless need to return a device for inspection or repair please pay strict attention to...

Страница 39: ...N Disposal must be carried out in accordance with legislation applicable in your country Separate collection of WEEE Waste Electrical and Electronic Equipment in the European Union Separate collection...

Страница 40: ...perature sensors features a measuring resistance with defined characteristics standardised in IEC 60751 The same is true for the tolerances The average temperature coefficient of a Pt100 is 3 85 x 10...

Страница 41: ...ction are at the same temperature no thermoelectric voltage is generated The degree of thermoelectric voltage also known as electromotive force EMF depends on the thermocouple material and the extent...

Страница 42: ...d Safety Instrumented Systems SIS HART 6 compliance The transmitters are fully compliant with the HART 6 protocol as well as the previous HART 5 HART 6 offers the possibility to receive diagnostic inf...

Страница 43: ...nce 2 wire adjustable wire resistance compensation RTD and resistance 3 wire negligible with equal wire resistance RTD and resistance 4 wire negligible Thermocouple and voltage negligible Supply volta...

Страница 44: ...mm2 AWG 16 no shielded cable required Inputs Outputs Input RTD Input RTD Input RTD Input RTD Pt100 IEC 60751 0 00385 200 850 C 328 1562 F Pt100 JIS C 1604 8 0 003916 Pt X 10 X 1000 IEC 60751 0 00385...

Страница 45: ...tion Compensation CJC Internal external Pt100 or fixed Input voltage Input voltage Input voltage Input voltage Range 10 1000 mV Minimum span 2 mV Customized linearization Up to 50 points Input impedan...

Страница 46: ...475 Emerson Management systems e g AMS Emerson and PDM Siemens EDD enabled systems DTM FDT enabled systems Approvals and certifications CE The device fulfils the statutory requirements of the EC direc...

Страница 47: ...d transmitter In head transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Dimensions mm inch a 33 0 1 30 b 7 0 0 28 c 44 5 1 75 d 24 0 0 95 Dimensio...

Страница 48: ...il mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Intrinsically safe transmitter Temperature class Ambient temperature Ta T6 40 C Ta 60 C 40 F Ta 140 F T5 40 C...

Страница 49: ...issible output load permissible RLoad U 10 0 022 Standard transmitter Figure 7 3 Output load diagram X Power supply U VDC Y Total output load R Intrinsically safe transmitter Figure 7 4 Output load di...

Страница 50: ...transmitter Rail mount transmitter Intrinsically safe transmitter TT 51 R Ex Output terminals 6 7 Input terminals 1 2 3 4 5 Ui Vmax 30 VDC U0 U0C 6 6 VDC Ii Imax 100 mA I0 ISC 26 4 mA Pi Pmax 900 mW...

Страница 51: ...f span per C T C type B 400 1800 700 1 0 C or 0 1 of span 2 0 005 of span per C T C type C 0 2315 200 1 0 C or 0 1 of span 2 0 005 of span per C T C type D 0 2315 200 1 0 C or 0 1 of span 2 0 005 of s...

Страница 52: ...F or 0 1 of span 2 0 003 of span per F T C type C 32 4199 360 1 8 F or 0 1 of span 2 0 003 of span per F T C type D 32 4199 360 1 8 F or 0 1 of span 2 0 003 of span per F T C type E 328 1832 90 0 45 F...

Страница 53: ...NOTES 8 53 TT 51 SERIES www krohne com 08 2015 4000754203 MA TT 51 R03 en Notes MA_OPTITEMP_TT_51_en_150828_4000754203_R03 book Page 53 Friday August 28 2015 10 54 AM...

Страница 54: ...8 NOTES 54 TT 51 SERIES www krohne com 08 2015 4000754203 MA TT 51 R03 en MA_OPTITEMP_TT_51_en_150828_4000754203_R03 book Page 54 Friday August 28 2015 10 54 AM...

Страница 55: ...NOTES 8 55 TT 51 SERIES www krohne com 08 2015 4000754203 MA TT 51 R03 en MA_OPTITEMP_TT_51_en_150828_4000754203_R03 book Page 55 Friday August 28 2015 10 54 AM...

Страница 56: ...mbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 10389 info krohne com KROHNE 08 2015 4000754203 MA TT 51 R03 en Subject to change without notice The current list of all...

Отзывы: