7 Maintenance and fault rectification
SU 600 • 4 … 20 mA signal conditioning instrument
30652-EN-150129
7 Maintenance and fault rectification
7.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
7.2 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
Maximum reliability is ensured. Nevertheless, faults can occur during
operation. These may be caused by the following, e.g.:
•
Measured value from sensor not correct
•
Voltage supply
•
Interference in the cables
The first measures to be taken are to check the input/output signals
as well as to evaluate the error messages via the display. The proce-
dure is described below. In many cases, the causes can be deter-
mined in this way and faults can be rectified.
The signal conditioning instrument and the connected sensors are
permanently monitored during operation and the values entered dur-
ing parameter adjustment are checked for plausibility. If irregularities
occur or in case of incorrect parameter adjustment, a fault signal is
triggered. In case of an instrument defect or line break/shortcircuit, a
fault signal is also triggered.
The fail safe relay deenergises in case of failure, the failure indication
lights and the current output jumps to 22 mA. In addition, one of the
following fault messages is outputted on the display.
Error code Cause
Rectification
E003
CRC error (error with
self-check)
– Carry out a reset
– Send instrument for repair
E014
Sensor current
> 21 mA or short-
circuit
– Check sensor, e.g. on failure
– Remove short-circuit
E015
Sensor in boot phase
Sensor current
< 3.6 mA or line
break
– Check sensor, e.g. on failure
– Remove line break
– Check connection of the sensor
E016
Empty/full adjustment
reversed
– Carry out a fresh adjustment
E017
Adjustment span too
small
– Carry out a fresh adjustment and
increase the distance between min.
and max. adjustment
E021
Scaling span too
small
– Carry out a fresh scaling, increase
the distance between min. and max.
scaling.
Reaction when malfunc-
tions occur
Causes of malfunction
Fault rectification
Fault message
Содержание SU 600
Страница 1: ...Operating Instructions SU 600 4 20 mA signal conditioning instrument Document ID 30652...
Страница 30: ...30 Notes SU 600 4 20 mA signal conditioning instrument 30652 EN 150129...
Страница 31: ...31 Notes SU 600 4 20 mA signal conditioning instrument 30652 EN 150129...
Страница 32: ...Subject to change without notice 30652 EN 150129...