16
5 Connecting to power supply
OPTISWITCH 5100 C, 5150 C • Contactless electronic switch
30428-EN-210701
5 Connecting to power supply
5.1 Preparing the connection
Always keep in mind the following safety instructions:
Warning:
Connect only in the complete absence of line voltage.
•
The electrical connection must only be carried out by trained,
qualified personnel authorised by the plant operator.
•
Always switch off power supply, before connecting or disconnect-
ing the instrument.
Note:
Install a disconnecting device for the instrument which is easy to
access. The disconnecting device must be marked for the instrument
(IEC/EN 61010).
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.
Connect the voltage supply according to the connection diagrams.
The electronics module SWE60C is designed in protection class I.
To maintain this protection class, it is absolutely necessary that the
earth conductor be connected to the inner earth conductor terminal.
Keep the general installation regulations in mind. Take note of the
corresponding installation regulations for hazardous areas with Ex
applications.
The data for power supply are specified in chapter "
Technical data
".
The instrument is connected with standard three-wire cable without
screen. If electromagnetic interference is expected which is above the
test values of EN 61326 for industrial areas, screened cable should
be used.
Make sure that the cable used has the required temperature resist-
ance and fire safety for max. occurring ambient temperature
Use cable with round cross-section. A cable outer diameter of
5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.
If you are using cable with a different diameter or cross-section,
exchange the seal or use a suitable cable gland.
In hazardous areas, use only approved cable connections for OPTIS-
WITCH 5100 C, 5150 C.
Take note of the corresponding installation regulations for Ex applica-
tions.
Cover all housing openings conforming to standard according to
EN 60079-1.
Note safety instructions
Take note of safety
instructions for Ex
applications
Voltage supply
Connection cable
Connection cable
for Ex applications
Содержание OPTISWITCH 5100 C
Страница 1: ...OPTISWITCH 5100 C 5150 C Handbook Vibrating Level Switch Contactless electronic switch ...
Страница 38: ...38 Notes OPTISWITCH 5100 C 5150 C Contactless electronic switch 30428 EN 210701 ...
Страница 39: ...39 Notes OPTISWITCH 5100 C 5150 C Contactless electronic switch 30428 EN 210701 ...