Manual OPTISENS CAC 050 / IAC 050
OPTISENS CAC 050 / IAC 050
8
2.
Electrical connection
You will find a detailed connection diagram on the following pages.
Before connecting the power supply check the information on the nameplate of the device!
ATTENTION
Input, output and control lines must be installed separate from each other and separate from power lines!
For inputs and outputs use screened lines and connect the screen on one side only.
The conductivity measurement is interference-sensitive. Use a special screened cable and over long
distances or in humid atmosphere additionally an impedance converter.
For the connection of the temperature sensor use a low-resistance cable with a large diameter.
When using the relays, mind that with inductive loads, interference must be suppressed. If that is not
possible, the relay must be protected at the terminal block in the converter by a resistance-capacitance filter
or, in case of direct current, by a free- wheeling diode.
Current up to
Capacitor C
Resistance R
60 mA
10 nF 260 V
390 Ohm 2 Watt
70 mA
47 nF 260 V
22 Ohm 2 Watt
150 mA
100 nF 260 V
47 Ohm 2 Watt
1.0 A
220 nF 260 V
47 Ohm 2 Watt