OPERATION
4
23
MFC 400
www.krohne.com
12/2017 - 4006097501 - AD MFC 400 Profinet R01 en
4.9.8 Totalizer 2
4.9.9 Status and Diagnostics
ID
Name
Data type
Remarks
66
Measurement
Unsigned8
Select measurement connected to the totalizer: Volume Flow,
Mass Flow, Concentration Mass Flow 1, Concentration Volume
Flow 1, Concentration Mass Flow 2, Concentration Volume
Flow 2
67
Function
Unsigned8
Off, Absolute Total, Incremental Total, Decremental Total
68
Damping [s]
Float32
Damping for measurement connected to the totalizer, based
on t63.
69
LFC Volume - Threshold
Float32
Low flow cutoff threshold if measurement is set to "Volume
flow".
Unit: selected by ID 50
70
LFC Volume - Hysteresis
Float32
Low flow cutoff hysteresis if measurement is set to "Volume
flow".
Unit: selected by ID 50
71
LFC Mass - Threshold
Float32
Low flow cutoff threshold if measurement is set to "Mass
flow".
Unit: selected by ID 51
72
LFC Mass - Hysteresis
Float32
Low flow cutoff hysteresis if measurement is set to "Mass
flow".
Unit: selected by ID 51
Table 4-21: Parameter group - Totalizer 2
ID
Name
Data type
Remarks
73
NE107 Proc. System Control
Unsigned8
NE107 mapping possible to:
- Information
- Maintenance Required
- Function Check
- Out Of Specification
- Failure
74
NE107 Conf. Totalizer
Unsigned8
75
NE107 Proc. Signal Low
Unsigned8
76
NE107 Proc. Two Phase Flow
Unsigned8
77
Two Phase Signaling Threshold
Float32
Process-dependent threshold of the 2 phase signal status
message
1
.
0 disables detection of 2 phase flow.
Table 4-22: Parameter group - Status and Diagnostics
1
For usage of concentration measurement, please order the "Concentration package".