IFC090, IFC090 i with FF
Troubleshooting
IFC090 FF 01/2005
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5
D-47058 Duisburg
Tel.: 0203-301 309
Fax: 0203-301389 · E-mail: [email protected]
Other possibly occuring statuses correspond to the PRIMARY_VALUE statuses. See 6.1.3 for details.
6.1.4 Integrator
Blocks
The follwowing table lists the block errors documented by the Integrator Blocks:
Error Code
Description
Action
Out of Service
Target mode is set
to
‘Out of Service
(OOS)’
If Automatic is the desired target mode, set
MODE_BLK
target
to
‘Automatic (Auto)’
Memory Failure
Device
memory
failure.
Replace signal converter or contact KROHNE service.
6.2
Transducer Block XD_ERROR
The Transducer Block has a special error parameter XD_ERROR. If this error displays the error ‘Electronics
failure’, the AD converter of the sensor seems to have problems. Please contact the KROHNE support team, if
this error remains.
6.3
Measurement Value Status
Besides the problems that are displayed in the BLOCK_ERR parameter of each block, the status of the
Transducer Block parameter PRIMARY_VALUE (the raw measurement value obtained from the device) can
provide further information on possible reasons for measurement problems.
The following table lists possible indications:
PRIMARY_VALUE
state
Description
Action
BAD:OutOfService:Not
Limited
Target mode is set
to
‘Out of Service
(OOS)’
If
Automatic
is the desired target mode, set
MODE_BLK
target
to
‘Automatic (Auto)’
BAD:DeviceFailure:Not
Limited
AD converter fatal
error.
Contact the KROHNE support team.
BAD:SensorFailure:Low
Limited
Measured value is
below the sensor
range.
Check instrument parameters and correct it if necessary. Error
messages deleted automatically.
BAD:SensorFailure:Hig
hLimited
Measured value is
above the sensor
range.
Check instrument parameters and correct it if necessary. Error
messages deleted automatically.
Pipe is empty.
Fill the pipe with media.
Uncertain:NonSpecific:
NotLimited
AD converter
warning.
Check instrument parameters and correct it if necessary. Error
messages deleted automatically.
Uncertain:NonSpecific:
Constant
Current mode is
‘Manual (Man)’
If
Automatic
is the desired mode, set
MODE_BLK
traget to
‘
Automatic
(Auto)’.
Uncertain:SensorConve
rsionNotAccurate:NotLi
mited
AD converter
overshooted.
Check instrument parameters and correct it if necessary. Error
messages deleted automatically.