Supplementary Documentation
Page 4 of 44
IFC090, IFC090 i with FF
Introduction
IFC090 FF 01/2005
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5
D-47058 Duisburg
Tel.: 0203-301 309
Fax: 0203-301389 · E-mail: [email protected]
1 Introduction
These instructions are supplementary to the “Installation and Operating Instructions IFC 090 K / F“. The details
depicted therein, in particular the Safety Information are valid and should be adhered to. The present
Supplementary Instructions provide additional information for the devices when being operated and connected
to a Foundation Fieldbus.
Note: Please set the controller to manual mode before changing parameters of the IFC 090.
The present Supplementary Instruction for the IFC 090 with Foundation Fieldbus- interface, plus a diskette with
the DD and CCF file are included in our scope of supply, in addition to those items delivered for the standard
device.
2 Installation and Operation
2.1
Technical Data IFC090 FF
Hardware
Physical
to IEC 61158-2 and the FISCO model
Bus characteristics:
9... 30 V; 0.3 A max.; 4.2 W max.
Base current
10 mA
FDE
bus with separate fault detection electronics
Fault current
6 mA; (fault current = max. continuous current – base current)
Starting current
lower than the base current
“Ex“ approval
EEx ia IIC T6 or EEx ib IIC/IIB T6 in conformity with the FISCO model
Connection
independent of polarity
Software
DD, CFF File
supplied on diskette, available also in the KROHNE Downlaod Center
Functional blocks
flow [m3/s], integrator 1 [m3], integrator 2 [m3]; units are default units
Operator control
local display and operator interface at device
2.2 Electrical
Connection
of Foundation Fieldbus Devices
Connect the bus cable as shown in the figure.
•
Connect the cable cores to terminals D and DI.. Polarity reversal will not have any effect.
•
The cable shield should be connected with minimum length to the FE functional ground.
•
The equipotential bonding conductor must be connected to the device by connecting it to FE functional
ground.