24 www.krohne.com 

04/2012

 

 ALTOSONIC V 

ELECTRICAL INSTALLATION

3

 

Construction 

The Flow Processor UFP-V, is an industrial type computer, e.g. Advantec Workstation AWS-
842T. The I/O modules are mounted on the front side of the I/O-rack and transfer the 
(intrinsically safe) process inputs to the flow processor. On the back side are the connections to 
the UFC-V field mounted converter unit, the custody transfer certified pulse output, the Modbus 
connection, as well as binary status outputs and control inputs. For custody transfer purposes 
the panel may be sealed. The optional printer connection is direct on the terminal of the 
workstation and is supplied with a DB9 connector. See figure for terminal side of the 
workstation). 

 

I/O rack input signals (front side) 

The I/O modules are interfacing with process instruments for: 
 

 

Temperature, Pt100 or 4…20 mA transmitters; 

 

Pressure 4...20 mA transmitters 

 

Density transmitters with frequency superposed on the loop current. 

 
Note: Modules may be intrinsically or non-intrinsically safe. 

 

Custody transfer certified I/O modules that may be used are: 

 

Made by MTL (Cenelec, FM and CSA Ex i certified modules) 
MTL 5073/4 

Pt 100 temperature input 

MTL 7206 

4 .. 20 mA loop powered transmitters 

MTL 7087 

4 .. 20 mA loop powered density transmitters 

 

Made by Phoenix (for non Ex circuits) 
MCR-T-UI 

Pt 100 temperature input 

MCR-CPS-I/I-44-E 

4 .. 20 mA loop powered transmitters 

 

Made by Pepperl & Fuchs 
KFD2-CD-Ex1.32-8 

4 .. 20 mA current output 

Module by KROHNE 

 

 
Data sheets of the different modules are not included because it is dependent of the ordered 
configuration. Connections are not renumbered so the data sheets of the modules and the 
equipment connected are needed for the planning of the installation. 
 

Connection of the body temperature sensor of the UFS-V to the I/O module  

Because the flow sensor UFS-V is mounted in a potential hazardous are an Ex-i certified I/O 
interfacing module MTL 5073/4 for the body temperature shall be used. The body temperature 
sensor terminals are interfaced as follows: 
 

MTL 5073/4   connection 
terminals 

UFS-V Pt 100   
connection terminals 

1 5 
4 7 
3 6 
5 8 

 

Содержание ALTOSONIC V

Страница 1: ...Processor Electrical Mechanical Installation Soware Version 0300 ALTOSONIC V Installation Manual ALTOSONIC V 5 beam ultrasonic flowmetering system Operating and installation instructions UFC V EEx Flo...

Страница 2: ...ge Install the product securely and stable Install and connect cabling proper to exclude damage or harmful situations If the instrument does not operate normally refer to the service instructions or r...

Страница 3: ...stem may lead to loss of warranty In addition the Terms and Conditions of Sale are applicable and are the basis for the purchase contract If flow meters need to be returned to KROHNE please note the i...

Страница 4: ...Certificate of system calibration data This instrument is developed and manufactured by KROHNE Altometer Kerkeplaat 12 3313 LC Dordrecht The Netherlands For information maintenance or service please...

Страница 5: ...3 Electrical installation 13 3 1 Overview of connections 13 3 2 Installation location and wiring considerations 13 3 3 Power connection 14 3 4 Connecting Flow Sensor to Flow Converter 15 3 5 Connecti...

Страница 6: ...its environment 1 2 Unpacking and inspection This product has been thoroughly inspected and tested before shipment and is ready for operation After carefully unpacking inspect for shipping damage bef...

Страница 7: ...d the supplied I O rack configuration may only be operated in a safe non hazardous area The I O rack contains the additional I O modules for a safe separation between hazardous and non hazardous envir...

Страница 8: ...the Operating and Installation Instructions for use in hazardous areas For the non hazardous area equipment UFP V and I O rack the following applies This product is designed for use in accordance with...

Страница 9: ...29 of the housing Use up to an altitude of 2000 m above sea level Operation ambient temperature range 0 C to 50 C Use with a relative humidity of 5 85 50 C non condensing Storage temperature range 20...

Страница 10: ...and regulations must be respected The sensor axis must be approximately horizontal even if the flowmeter is installed in slightly ascending horizontal pipe runs The position of the flow sensor in the...

Страница 11: ...eter of the flanges of the flow sensor Correct gaskets shall be used If inlet and outlet sections are ordered they will be used during the calibration and must be installed identically in the final ap...

Страница 12: ...g device to keep the electronics within its working temperature range If because of indirect heating e g by sunlight the housing temperature can become 65 C a sunshade is recommended to prevent the el...

Страница 13: ...ons Do not kink the cables Provide a water drip point U bend in cable Conduits The described standard version of ALTOSONIC V is equipped with cable glands for the use of harmonized cable In countries...

Страница 14: ...ter UFC V and Flow Sensor UFS V PE Protective conductor incorporated in power supply cable Coax Sensor cables factory supplied Bonding wire Connection cable cross section 4 mm2 10 AGW Cu equipped with...

Страница 15: ...conductor protective earth conductor shall be connected to the indicated PE terminal in the signal converter housing Terminal Description Connect to Mains voltage 115 230V AC I O rack X10b with IEC so...

Страница 16: ...ATION 3 Connection box on Flow Sensor UFS V and shield grounding clamp On the side of the Flow Converter UFC V the cables must be connected in the same way as in the Flow Sensor UFS V but on connector...

Страница 17: ...04 2012 www krohne com 17 ALTOSONIC V ELECTRICAL INSTALLATION 3 Connector X1 X2 of Flow Converter UFC V 24 VDC Connector X1 X2 of Flow Converter UFC V 110 230 VAC...

Страница 18: ...in the I O rack to the MTL5073 module A1 as shown below This connection has to be made with a shielded 4 wire cable not supplied In the Flow Sensor UFS V and the I O rack Flow Computer UFP V this cab...

Страница 19: ...wire must also be connected with the shield to the shield connectors on both sides The cable has to be connected according to the table below UFC V X1 Wire I O rack UFP V connection terminal position...

Страница 20: ...ed with flowmeter 3 7 Connecting the I O rack to the Flow Computer UFP V For connecting the Flow Computer UFP V I O rack to the Flow Computer UFP V the pre wired connectors on the Flow Computer UFP V...

Страница 21: ...uts Mp103 card DB9 Connector 1 TTL compatible Umax 12 V Imin 1mA Imax 10mA Relay outputs MP103 card DB9 Connector 2 Switchable Umax 150Vdc 125Vac Imax 0 2A Current output MP103 card DB9 Connector 3 Ac...

Страница 22: ...MP103 Analog inputs AD812 card PCLD 780 wiring board Pmax limit for used 250 ohm resistors 0 2 W Maximum Overvoltage continuous 7V Usually connected through barriers Analog outputs AD812 card PCLD 78...

Страница 23: ...d the auxiliary apparatus like temperature pressure and density measuring instruments The results are displayed on the screen and represented in a train of output pulses with a calibrated one pulse vo...

Страница 24: ...current Note Modules may be intrinsically or non intrinsically safe Custody transfer certified I O modules that may be used are Made by MTL Cenelec FM and CSA Ex i certified modules MTL 5073 4 Pt 100...

Страница 25: ...ire cross section chosen to fit The field cabling shall be according to the local regulations and practice The instrument is constructed in accordance with the applicable European directives LVD 73 23...

Страница 26: ...d the I O communication to external apparatus see figure x In the table below you can find the detailed list of the terminal numbers and its function Further detailed information of the functions refe...

Страница 27: ...n For factory use only 21 22 Stop calibration 23 24 Failure signal output 25 26 Warning signal output 27 28 Forward flow direction low flow cut off forward 29 30 Reverse flow direction low flow cut of...

Страница 28: ...ith the UFC V Flow Converter unit and is factory set The second channel is defined for Modbus communication with external systems Flow data and relevant auxiliary signals are available A user configur...

Страница 29: ...in line with the following model confirming that the flow meter is safe to handle If the flowmeter has been operated with toxic caustic flammable or water polluting liquids you are kindly requested T...

Страница 30: ...30 www krohne com 04 2012 ALTOSONIC V SERVICING 4 4 2 Spare parts For more information please contact KROHNE...

Страница 31: ...Analysis products Measuring systems for the oil and gas industry Measuring systems for sea going tankers Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 D 47058 Duisburg Germany Tel 49 0 203 3...

Отзывы: