General information 

1.1 

Description 

The INT69 YF Diagnose tripping device is a versatile universal protection device. Various temperature, 
voltage, leakage/resistance measurement and analogue signal inputs are available in a single module 
for monitoring electrical components. Parametrization enables protection function and response 
settings to be adapted flexibly to suit the application. The INT69 YF Diagnose saves operating and 
fault data in a non-volatile memory. This data can be read out and evaluated for diagnostics purposes. 
This tripping device is used primarily for the protection of pumps. 

 

1.2 

Additional documents 

In connection with these operating instructions, the following documents should be observed: 

• 

The data sheet for the Diagnose diagnostics device 

• 

General or application-specific SOPs within the context of the Health and Safety at Work Act 
and the Ordinance on Work Equipment and Tools 

• 

Accident prevention regulations 

• 

Legal regulations 

• 

Local regulations 

 

1.3 

Symbols used 

Meaning of the symbols and safety notices used in this document. 
 

Please note that a safety symbol is never a substitute for a safety notice in text form - 

therefore always read all safety notices! 

This document contains information that must be observed to avoid personal injury and equipment damage. 
Safety information to avoid personal injury is indicated by means of a color code with a warning 
triangle and a signal word defined in accordance with ANSI Z535.6-2006: A1.2. 
The signal words are classified according to ANSI Z535.6-2006: C4.2. 
Depending on the degree of risk, the notices are shown as follows: 
 

This indicates that death or serious injury will occur if the relevant precautions are not 
taken here! 

 

This indicates that death or serious injury may occur if the relevant precautions are not 
taken here 

 

This indicates that minor injury may occur if the relevant precautions are not 
taken here! 

 

This denotes information and tips for use. It does not represent a safety notice. 

 
The text of a safety notice is divided into: 
_________________________________________________________________________________ 

Description of the nature/source of the danger 

 

Description of the consequences of disregarding the safety notice.

 

  Measures for avoidance 

_________________________________________________________________________________ 

 

 

Содержание INT69 YF Diagnose Extended 20A701P081

Страница 1: ...p protection module INT69 YF Diagnose Phase monitoring of 3 1x Motor temperature 2x Bearing or media temperature Switching frequency limitation Leakage LED status display Diagnose Interface Relais output Analog input ...

Страница 2: ... 1 Motor temperature 7 4 4 2 Temperature monitoring 7 4 4 3 Leakage monitoring 8 4 4 4 Phase monitoring 8 4 4 4 1 Phase failure 8 4 4 4 2 Phase sequence 8 4 4 4 3 Phase asymmetry 8 4 4 4 4 Undervoltage and overvoltage 8 4 4 5 Analog input 8 4 5 Outputs 9 4 5 1 Alarm relay 9 4 5 2 Warning relay 9 4 5 3 Diagnostics port 9 4 5 4 Duo LED 9 4 6 Switching frequency limits 10 5 Commissioning 11 5 1 Wirin...

Страница 3: ...t Please note that a safety symbol is never a substitute for a safety notice in text form therefore always read all safety notices This document contains information that must be observed to avoid personal injury and equipment damage Safety information to avoid personal injury is indicated by means of a color code with a warning triangle and a signal word defined in accordance with ANSI Z535 6 200...

Страница 4: ...oper operation of pumps Possible functions include monitoring voltage power network temperature and leakage Any 0 20 mA sensor can also be connected for example for pressure or vibration monitoring The relevant details can be found in chapter 4 2 Technical data Any use other than or going beyond this shall not be deemed as intended use 2 3 Personnel requirements Improper installation commissioning...

Страница 5: ...aging or in suitable individual packaging 3 4 Disposal All associated components must be disposed of in accordance with your country s applicable disposal regulations For Germany this includes Electrical waste Equipment bearing this symbol is subject to European Directive 2002 96 EC All waste electronic and electrical equipment must be disposed of separately from domestic waste Ask your city counc...

Страница 6: ...s in series alternatively 1 9 PTC sensors as per DIN 44081 DIN 44082 in series 1 8 kΩ 4 5 kΩ 20 2 75 kΩ 20 30 m 20 Ω 20 kΩ Temperature measuring circuit Type Measuring range Resolution Accuracy Short circuit monitoring Open circuit monitoring Pt100 50 to 300 C 1 K 5 of measuring range final value 20 Ω 400 Ω Temperature measuring circuit Type Measuring range Resolution Accuracy Short circuit monito...

Страница 7: ...estart delay Configurable Reset of lock or restart delay Network reset 5 s only possible once any faults have been rectified Relay Contact Mechanical service life AC 240 V 2 5 A C300 min AC DC 24 V 20 mA Approx 1 million cycles Interface Diagnostics port DP Degree of protection as per EN 60529 IP20 Connection type Tension spring connection PUSH IN 0 2 2 5 mm2 Housing material PA 66 GF 30 Fixing Co...

Страница 8: ... delay All inputs can also be deactivated 4 4 1 Motor temperature For motor temperature monitoring terminals T1 and T2 PTC PT100 PT1000 or bimetal sensors can be parameterized PTC selected When the nominal response temperature of the PTC sensors installed in the motor winding is reached switch off occurs after a static evaluation process Pt100 Pt1000 selected When the parameterized switch off temp...

Страница 9: ...is deactivated for approx 2 s to prevent unwanted switch off due to the machine running temporarily in reverse With the phase input it is possible to read in up to 690 V AC at a frequency converter capacity of 20 100 Hz To ensure adequate separation between the device and the phases the phases are read in via a high resistance input 4 4 4 1 Phase failure Monitored throughout the entire motor runti...

Страница 10: ...t 1st blinking sequence LED red 2nd blinking sequence LED orange Description 1 1 Motor temperature Static switch off permissible winding temperature exceeded 1 4 Motor temperature Sensor input detected an open or short circuit 2 1 Phase monitoring Incorrect phase sequence 2 2 Phase monitoring Phase failure asymmetry 2 3 Phase monitoring Undervoltage overvoltage 3 1 Temperature input 1 Static switc...

Страница 11: ...ocesses of a superordinate switching unit of the machine depending on the set time unit and switches off if the set value is exceeded A restart occurs in accordance with the conditions of the restart delay Switching frequency limits are only available if the phase monitor is active ...

Страница 12: ...11 5 Commissioning 5 1 Wiring 5 1 1 Circuit diagrams First level front terminals ...

Страница 13: ...e control cabinet or control box on to a 35 mm standard rail 2 Connect the supply voltage and sensors according to the circuit diagrams Applying the supply voltage without sensors being connected is detected as a fault and stored in the internal memory of the diagnostics device ...

Страница 14: ... sensor connection into the relevant hole and then loosen the terminal again 4 To prevent future faults during reconnection or maintenance the push in spring terminals can be individually coded To do this remove the terminal from the device and pull the relevant pins out of the device using fine pliers Then insert the pins in the places provided on the terminal ...

Страница 15: ...Each pin can now be separately coded together with its counterpart in the terminal For this use a flat head screwdriver to move the pins inserted in the terminal into one of the four possible positions Pins ...

Страница 16: ...tor app More about the KRIWAN INTspector app in chapter 6 2 5 2 1 Parameter table Parameter name Setting range Unit Min Max Motor temperature 1 Sensor type Switch off temperature Warning temperature Hysteresis Trip delay Restart delay Lead correction Deactivated 100 100 0 0 1 0 0 PT100 300 300 300 3600 Locked 100 C C K s s Ω Temperature 1 Sensor type Switch off temperature Warning temperature Hyst...

Страница 17: ...e restart delay Operating mode overvoltage Overvoltage limit 1 Overvoltage limit 2 Overvoltage hysteresis Overvoltage limit 1 trip delay Overvoltage limit 2 trip delay Overvoltage restart delay Deactivated Phase neutral 0 0 Deactivated 1 1 1 0 1 0 Deactivated 100 100 1 0 1 0 1 0 Deactivated 0 1 1 1 0 1 0 Active Phase phase 100 Locked Active 100 100 99 360 Locked Limit 1 warning 690 690 600 360 360...

Страница 18: ...tection with communication function The app enables data stored by the protection device to be read out directly to the system This gives you access to the fault memory counter enabling you to assess the current system status and view operating data The app can also be used to create a report in PDF format which can then if required be forwarded directly to your customers With parameterization mod...

Страница 19: ...18 KRIWAN INTspector app Android iOS Windows ...

Страница 20: ...information 2 Settings Language etc 3 Read DP data PDF report The app can also be used to create a PDF report which can then if required be forwarded directly to customers Current settings Change parameters Connection via Bluetooth USB Confirmation of the change INTspector homepage Diagnostics data Overview Module view No fault Module view Warning Connect via Bluetooth This function requires a Blu...

Страница 21: ...All set parameters are met Motor inactive due to active fault Links Click to jump directly to the pages INTspector homepage Diagnostics data Overview Module view Alarm Parameterization mode Overview Current settings Change parameters Connection via Bluetooth USB Confirmation of the change Overview Connection via Bluetooth USB Module view No fault Module view Warning Module motor temperature Sensor...

Страница 22: ...red permanently no reset after network reset INTspector homepage Diagnostics data Overview Connection via Bluetooth USB INTspector homepage Diagnostics data Module view Alarm Parameterization mode Overview Current settings Change parameters Confirmation of the change Module view No fault Module view Warning Module view Alarm Parameterization mode Overview Current settings Change parameters Confirm...

Страница 23: ...parameter by clicking on it Module view Warning Overview Connection via Bluetooth USB Module view Alarm INTspector homepage Parameterization mode Diagnostics data Overview Current settings Change parameters Confirmation of the change Module view No fault Module view Alarm INTspector homepage Parameterization mode Diagnostics data Overview Current settings Change parameters Confirmation of the chan...

Страница 24: ...rameters Overview Connection via Bluetooth USB Module view Warning Overview Connection via Bluetooth USB Module view Alarm INTspector homepage Parameterization mode Diagnostics data Overview Current settings Change parameters Confirmation of the change Module view No fault Module view Warning Module view Alarm INTspector homepage Parameterization mode Diagnostics data Overview Current settings Cha...

Страница 25: ...o confirm the changed parameters Confirm with OK Module view Alarm INTspector homepage Parameterization mode Diagnostics data Overview Current settings Change parameters Confirmation of the change Module view No fault Module view Warning Overview Connection via Bluetooth USB ...

Страница 26: ...EU Declaration of Conformity See www kriwan com Type Designation Article number Gateway INT600 DB Gateway Bluetooth gateway 02S377S021 INT600 DU Gateway USB gateway 02S365S21 INT600 DM Gateway Modbus gateway 22S371 DP cable DP cable angled at both ends 10 m FK02098069 DP cable angled at both ends 1 m FK02098063 DP cable angled at both ends 30 cm FK02098062 KRIWAN Industrie Elektronik GmbH Allmand ...

Отзывы: