Kramer CED Скачать руководство пользователя страница 3

PIPING

All piping must be clean and dry.  Keep it capped to prevent dirt and moisture from entering.
Do not leave piping open to the atmosphere overnight.   When brazing, keep dry nitrogen
flowing through the lines to prevent internal oxide and scale formation.  Use a high
temperature silver brazing alloy.   An off cycle pumpdown, with the room thermostat controlling
the liquid solenoid, is recommended, and is mandatory to maintain compressor warranty on
electric defrost systems.

Suction lines should slope a MINIMUM of 1/4 inch per foot in the direction of flow to insure oil
return.  “P” traps must be used at the bottom of every suction riser and at 15 foot intervals.  To
control compressor superheat and return gas temperature it may be necessary to insulate the
suction line, especially if long line runs are subjected to high ambient temperatures.  Liquid-
suction line heat exchangers are often used with electric defrost systems and are highly
recommended to obtain optimum performance.

See page 6 and 7  for line sizing recommendations.  Take caution not to undersize lines.  The
liquid solenoid should be installed near the expansion valve inlet, inside the refrigerated space
or in the evaporator end housing.  Secure the liquid line at the evaporator.  When the liquid
solenoid opens and closes the liquid line experiences a “SHOCK” and tends to move
forcefully.  Without proper support, the joints at the solenoid, expansion valve, distributor, and
distributor leads will fracture.  Line supports are inexpensive compared to refrigerant loss and
downtime.  All piping must be supported to prevent vibration and breaking.  Tube clamps
should have a cushion surface for protecting the tubing.

Expansion valves should be selected from the valve manufacturers literature.  If liquid
subcooling is present, be sure to use the correction factor to determine the correct size valve.
Avoid oversizing the valve which can cause hunting and floodback. On KS Electric Defrost
Systems, always use the expansion valves supplied with each evaporator. Read and retain the
expansion valve instructions.  The expansion valve bulb must be clamped securely on the side
of a horizontal run of suction line, before any traps, preferably at the 4 o’clock or 8 o’clock
position.  The bulb must be in complete contact with clean copper tube and must not bridge
any uneven surface.  Use the bulb clamp supplied with the expansion valve.  Take care not to
distort or crush the expansion valve bulb when tightening the clamp.  See page 9 for
expansion valve adjustment recommendations.

The drain line should run directly from each evaporator and exit the freezer as quickly as
possible.  It should be pitched a MINIMUM  of 4 inches per foot.  The drain line must always
be as large as the drain pan connection or larger.  Do not reduce the drain line size.  Some
evaporators defrost quickly and therefore a large volume of condensate must be drained
rapidly.  There should be no traps or sharp changes of direction within the freezer.  Drain lines
should have a trap where the ambient is always above 33°F or be protected from freezing by
continuous heating.  The entire drain connection, drain line and trap may be heated and
insulated.  Traps will prevent warm, moist air from being drawn up through the drain line,
which will form ice in the drain pan or on the bottom of the coil.  Drain lines should run to an
open drain.  They should never be directly connected to a sewer.  Never let the condensate
run onto walkways or floors creating a safety hazard.  Inspect the drain pan and connection
periodically to be sure it is clean and clear for free draining.

3

Содержание CED

Страница 1: ...812 SEPTEMBER 1999 NEW KRAMER ELECTRIC DEFROST EVAPORATORS LPE LVE MSE CSE HSE CED KED INSTALLATION START UP AND MAINTENANCE INSTRUCTIONS 14230 Lochridge Blvd Covington Georgia 30014 770 778 5800 Fax...

Страница 2: ...MSE models are recommended for room temperatures to 20 F model CED and KED to 30 F and model HSE to 10 F Model CED and KED are available with D type direct drive fans as standard or an optional PP typ...

Страница 3: ...uld be selected from the valve manufacturers literature If liquid subcooling is present be sure to use the correction factor to determine the correct size valve Avoid oversizing the valve which can ca...

Страница 4: ...ainst a wall or directly on the floor Always leave 1 or more inches of air space along side walls and each end wall space should be equivalent to the evaporator height or more Do not locate evaporator...

Страница 5: ...not to scale No doors at side or back of evaporators Back wall H H 2 x H H Side Evaporator wall Air Air 5 x H Side Alternate wall Door location See Table above for H dimension Door Front wall 5 EVAPO...

Страница 6: ...1 3 8 1 5 8 1 3 8 1 5 8 2 1 8 1 2 1 2 5 8 60000 75000 1 1 8 1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 3 8 1 3 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 1 2 5 8 5 8 75000 90000 1 3 8 1 3 8 1 5 8 1 3 8 1 5 8 1...

Страница 7: ...1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 2 1 2 5 8 48000 60000 1 1 8 1 3 8 1 3 8 1 1 8 1 3 8 1 5 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 2 5 8 5 8 60000 75000 1 1 8 1 3 8 1 5 8 1 3 8 1 5 8 1...

Страница 8: ...n shipment Spin each fan blade to be sure it turns freely FIELD WIRING Terminal Block H1 H2 H3 3 N X 4 M3 HEATER SAFETY DEFROST TERMINATION Brown Yellow MOTORS and CAPACITORS FAN DELAY Brown Use only...

Страница 9: ...edium frost load air circulation is still good and coils defrost best Defrosting with a very light frost load can cause steaming Allowing a coil to become heavily frosted can reduce air circulation an...

Страница 10: ...iver Pressure_________PSI Evaporator Frost Load Light o Medium o Heavy o ___________________ Time since last defrost_____hours Timer set ____ defrost per day _____ minute Fail Safe DEFROST Check Heate...

Страница 11: ...006009 30 202136007 Defrost Termination Std 103079010 103079010 103079010 Adjustable DTFD is Fan Delay Std 103079009 103079009 103079009 standard on CED KED Adjustable DTFD Optional 204464037 20446403...

Страница 12: ...510 3 206240 005 240 3538 3 206240 019 460 3249 CED 6 KED 4 450 620 400 550 12 113100 115 800 2 113095 230 725 850 1070 750 950 12 113101 115 1150 2 113096 230 660 1360 1200 26 113102 115 1070 4 1130...

Отзывы: