16
KraftPowercon Sweden AB, Hjalmar Petris väg 49, S-352 46 Växjö, Sweden, Tel: +46 470-705200, Fax: +46 470-705201,
www.kraftpowercon.com
5.2.3.5
<Indication table
Indication
Interpretation
ON
STBY
AC
OK
DC
OK
ALARM
Green
Put out Green Green
Put out Normal operation
Green
Put out Green Green
Red
1. U
OUT
low, 50-82% of U
NOM
2. I
OUT
limited due to high temperature
3. Fan fault
Green
Put out Green
Put
out
Red
U
OUT
low, <50% of U
NOM
Green
Put out
Put
out
Put
out
Red
Mains fault
Flash
Put out Green
Put
out
Red
1. External blocking
2. HVSD tripped, waiting for restart
attempt
3. Turned off due to high temperature
Put out
Put out Green
Put
out
Red
Turned off due to tripped HVSD
Put out
Put out
Put
out
Put
out
Red
Turned off due to tripped HVSD + mains
fault
Put out
Orange Green
Put
out
Red
Normal standby
Put out
Orange
Put
out
Put
out
Red
Mains fault in standby state
Put out
Put out
Put
out
Put
out
Put out No mains supply
5.3
MONITORING UNIT PCM2
The operator panel is the visible part of the
monitoring unit PCM2. It is composed of a
display, push-buttons and a led-lamp. Operation
is described in the
Manual for monitoring unit
PCM2
.
When measuring the battery voltage you should avoid measuring directly at the battery
terminals due to the risk of arcing in the event of a possible short circuit. Use the short-circuit
protected voltmeter terminals on the front panel instead. The voltmeter terminal fits a standard
4 mm measuring pin. To avoid measurement errors, the voltmeter used should have high ohms,
10 Mohm or better.