9
KraftPowercon Sweden AB, Hjalmar Petris väg 49, S-352 46 Växjö, Sweden, Tel: +46 470-705200, Fax: +46 470-705201,
www.kraftpowercon.com
Ripple current................................................. <1 % of rated current
Efficiency, typical .......................................... >92 % at 3x400 V
AC
Other, see table in section 3.1
3.3
ENVIRONMENTAL DATA
Class of enclosure ......................................................... IP21 as per EN 60529
Cooling............................................................................ Temperature controlled fans in rectifier
modules, otherwise natural convection
Ambient temperature .................................................. 0 to +40 °C
Storage temperature..................................................... -40 to +70 °C
Humidity ........................................................................ <90 % RH, non-condensed
Altitude a.s.l................................................................... <2000 m
Noise level at +20 °C, 25% load ................................. 50-58 dBA depending on number of rectifier
modules
3.4
MECHANICAL DATA
Design ....................................... Floor cabinet with 19” rack frame
Placement ................................. Standing on floor indoors in dry and clean area
Weight ....................................... See table in section 3.1
Dimensions .............................. Cubicle type F27: 1361/600/600 mm (h/w/d),
Cubicle type F41: 2053/600/474 mm (h/w/d),
Cubicle type S39: 2100/840/654 mm (h/w/d),
Colour ....................................... RAL 7035 light grey
Cable inlet ................................ From above or beneath (F27, F41)
From beneath, above as option (S39)
3.5
CONFORMITY WITH STANDARDS
EN 60529 ................................ Protection degree IP21
EN 50178 ................................ LVD. Electronic equipment, including power electronics in electrical
power installations.
EN 50272-2 ............................ Safety requirements for secondary batteries and battery installations
EN 61000-6-2 ......................... EMC. Immunity of equipment in an industrial environment
EN 61000-6-4 ......................... EMC. Emission from equipment in an industrial environment