TECHNICAL DATA
3.1
ELECTRICAL DATA
3.1.1
Range
PRX can be equipped with one or two rectifier modules.
PRX Rectifier
module
U
NOM
I
RATED
Mains
power
*1
Mains
current
*1
Mains
fuse
*2
Power
loss
*3
I
RATED
Model
designation
(V
DC
) (A) (VA) (A
RMS
) (A) (W)
Number
of
modules (A)
Model
designation
PRX 24/20
20
670 3.4 10 97 1 20
L0500B-IW
PRX 24/40
40
1340
6.8
10
189
2
20 L0500B-IW
PRX 24/60
24
60
1960 10 16 192 1 60
V1500B
PRX 48/12
12
800
4.1
10
97
1
12 L0600A-IW
PRX 48/24
24
1600 8.2 10 189 2 12
L0600A-IW
PRX 48/25
25
1600
8.2
10
161
1
25 L1250A-IW
PRX 48/50-1
50
3150 16.1 20 317 1 50
L2500A-IW
PRX 48/50-2
48
50 3200 16.4
20
317
2 25
L1250A-IW
PRX 110/10
10
1410 7.2 10 144 1 10
L1250K
PRX 110/20
110
20 2820 14.4
16
283
2 10
L1250K
PRX 125/9
9
1410 7.2 10 144 1 10
L1250K
PRX 125/18
125
18
2820 14.4 16 283 2 10
L1250K
*1
: max at 195 V
AC
*2
: recommended value
*3
: type at 230 VAC and full load. Also includes monitoring unit.
3.1.2
Common electrical input data
Rated voltage ...........................................110
*1
/115
*1
/120
*1
/220/230/240 V AC 1- phase
Frequency .................................................47 – 63 Hz
Power factor..............................................> 0.95 at 230 V
AC
, full load
Connection screw terminal block..............0.14 – 4 mm
2
*1
: Only applies to certain models, see
Electrical data for rectifier module
.
3.1.3
Common electrical output data
Voltage regulation (static)..........................<±0.5% of nominal output voltage
Voltage regulation (dynamic) ....................<±1% within 3 seconds, 0-100 / 100-10 % load change
Current regulation .....................................<±1% of rated current
Setting range, current limit .......................0 - 100 % of rated current
Ripple voltage ...........................................<0.1 %
RMS
Ripple current ...........................................<1% of rated current
Efficiency, typical .....................................>90 % at 230 V
AC
Connection screw terminal block..............1.5 - 35 mm
2