8
KraftPowercon Sweden AB, Hjalmar Petris väg 49, S-352 46 Växjö, Sweden, Tel: +46 470-705200, Fax: +46 470-705201,
www.kraftpowercon.com
3.1.4
Electrical data for rectifier module
Output data
Input data
U
NOM
Setting
range
I
RATED
Voltage
range
Mains
power
*1
Mains
current
*1
Model
designation,
rectifier
module
(V
DC
) (V
DC
)
(A) (V
AC
) (VA)
(A
rms
)
Power
loss
*2
L0500B-IW
20
85 - 295
670
3.4
92
V1500B
24
21 – 28
60
180 - 264
1960
10.0
187
L0600A-IW
12
85 - 295
800
4.1
92
L1250A-IW
25
85 - 295
1600
8.2
156
L2500A-IW
48
42 - 56
50
150 - 295
3150
16.1
312
L1250K
110/125
97.5 - 145
10
90 - 300
1410
7.2
139
*1
: max at 195 V
AC
*2
: type at 230 V
AC
and full load
3.2
Environmental data
Class of enclosure ..................................................IP21 as per EN 60529
Cooling ..................................................................Temperature controlled fans in rectifier
modules
Ambient temperature (specified data applies).........0 to +40 °C
Storage temperature ..............................................-40 to +70 °C
Humidity ...............................................................<90 % RH, non-condensed
Altitude above sea level ........................................<2000 m
Noise level at +20 °C, fully equipped ....................<54 dBA
3.3
Mechanical data
Design................................... Wall cabinet
Arrangement ........................ On a wall indoors in dry, clean room
Weight .................................. 13 kg, fully equipped
Dimensions .......................... 340/245/227 mm (h/w/d), see also dimension diagram
Colour................................... RAL 7035 light grey
Cable inlets ........................... From underneath
3.4
Conformity with standards
EN 60529........................... Class of enclosure IP21
EN 50178........................... LVD. Electronic equipment, including power electronics in electrical
power installations.
EN 50272-2 ....................... Safety requirements for secondary batteries and battery installations
EN 61000-6-2 .................... EMC. Immunity for industrial electronics
EN 61000-6-3 .................... EMC. Emission standard for commercial and light-industrial
environments