Kozy-World FMK2501 Скачать руководство пользователя страница 12

  1 2

TROUBLE  SHOOTING

Continued

OBSERVED  PROBLEM

POSSIBLE CAUSE

REMEDY

ODS/pilot  lights  but  flame  goes  out
when  control  knob  is  released.

1.    Control    knob  not  fully  pressed  in.
2.    Control  knob  not  pressed  in  long
       enough.
3.    Equipment shutoff valve not fully open.
4.    Thermocouple    connection    loose
       at  control  valve.
5.    Pilot  flame not touching thermocouple.
        This  allows  thermocouple  to  cool
      causing the pilot  flame  to   go  out.
     This problem  could  be  caused  by
      one or both of the following:
       A)   Low  gas  pressure.
       B)   Dirty  or  partially  clogged ODS/
              pilot.
6.   Thermocouple  damaged.
7.   Control  valve  damaged.

1.    Press in control knob all the way.
2 .    After    OD S /p ilo t    lig h ts,      k eep

c o n tro l  k n o b   p r essed   in   fo r  3 0
seconds.

3.    Open  equipment  shutoff  valve all the
        way.
4 .     H a n d   t ig h t en   u n t il  s n u g ,   t h e n

tighten 1/4  turn more.

5.      A)  Contact  local  propane/LP  gas

company.

           B)   Clean ODS/pilot (see  Cleaning

and Maintenance, page 10 ) or replace
CDS/pilot  assembly.

6.    Replace  thermocouple.
7.    Replace  control  valve.

Burner does not light after  ODS/pilot   is
lit.

1.    Burner orifice is clogged.
2.   Inlet  gas  pressure  is  too  low.
3.   Burner  orifice  diameter  is  too  small.
4.   Thermocouple   leads   disconnected
      or improperly connected.

1 . C l e a n   b u r n e r   ( s e e  

C l e a n i n g

     and   Maintenance

, page 10) or  replace

     burner orifice.
2.  Contact    local     propane/LP    gas
      company.
3.   Replace  burner  orifice.
4.   Reconnect leads.

Delayed   ignition  burner.

1.   Manifold  pressure  is  too  low.
2.   Burner orifice is clogged.

1.   Contact   local  gas company.
2.    Clean    burner  (see 

Cleaning    and

       Maintenance, 

page 10).

Burner  backfiring  during  combustion.

1.   Damaged  burner.
2.   Gas  regulator  is  defective.

1.   Clean  burner  orifice  (see  Cleaning
       and  Maintenance, page 10).
2.   Replace  gas  regulator.

Slight   smoke   or   odor   during  initial
operation.

1.   Residues  from  manufacturing
       processes.
2.   Not enough air.
3.   Gas  regulator is defective.

1.    Problem  will stop after a few hours
       of operation.
2.   Check  burner  for  dirt  and  debris.
       If  found, clean  burner (see Cleaning
       and  Maintenance, page 10).
3.    Replace  gas  regulator.

Dark    residue    on  logs    or    inside    of
fireplace.

1.   Improper  log  placement.
2.   Air holes at burner inlet are blocked.
3.   Burner flame holes are blocked.

1.    Properly  locate  logs  (see 

Installing

Logs

,  page  9).

2.   Clean out air holes at burner inlet.

Periodically  repeat  as  needed.

3.   Remove blockage or replace burner.

Heater    produces    a      clicking/ticking
noise  just  after  burner  is  lit  or  shut off.

1.  Metal  expand ing  w hile  h eating   or
     contracting  while  cooling.

1.   This      is     common      with      most
        heaters.  If    noise    is    excessive,
        contact    qualified  service  person.

Содержание FMK2501

Страница 1: ...s appliance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer World Marketing of America Inc P O Box 192 Rt 22 West Mill Creek PA 17060 KOZY WORLD PHONE NUMBER 814 643 1775 http www worldmkting com R Safety Information Warnings 2 Air for Combustion and Ventilation 4 Installation 6 Operating heater 9 Cleaning Maintenance 10 Tr...

Страница 2: ...r ornaments such as pine cones vermiculite or rock wool Using these added items can cause sooting Do not add lava rock around base Rock and debris could fall into the con trol area of heater After servicing always replace screen before op erating heater 7 You must operate this heater with the heater screen in place Make sure heater screen is in place before running heater 8 This heater is designed...

Страница 3: ...ge If fireplace or logs are damaged promptly inform dealer where you bought the fireplace from PRODUCT FEATURES SAFETY PILOT This heater has a pilot with an Oxygen Depletion Sensing ODS safety shutoff system The ODS pilot is a required feature for vent free room heaters The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYSTEM This heater has a piezo ignitor This sy...

Страница 4: ...ning if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms 1 Determine the volume of the space length width height Length Width Height cu ft volume of space Example Space size 20ft length ...

Страница 5: ... room unconfined Figure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr WARNING If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by one of the methods described in th...

Страница 6: ...t to vinyl or cloth wall coverings or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may dis color walls IMPORTANT Vent free heaters add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew See Air for Combustion and Ventilation pages 4 through ...

Страница 7: ...mmonly known as wellhead gas CAUTION Only use a new black iron or steel pipe Internally tinned cop per tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur Installation must include an equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach...

Страница 8: ...xture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Pressure Testing Heater Gas Connections 1 Open equipment shutoff valve see Figure 8 Figure 9 Checking Gas Joints INSTALLATION Continued CHECKINGGASCONNECTIONS 2 Open gas supply valve 3 Make sure co...

Страница 9: ...Turn control knob clockwise to the OFF position 4 Wait five 5 minutes to clear out an y g as Th en smell for gas including near the floor If you smell gas STOP Follow B in the safety information on page 2 If you don t smell gas go to the next step 5 Turn control knob counterclockwise to the PILOT position Press in control knob for five seconds see Figure 11 l Note You may be running this heater fo...

Страница 10: ...heater off see To Turn Off Gas to Appliance page 9 l see Troubleshooting pages 11 through 12 CLEANING AND MAINTENANCE WARNING Turn off heater and let cool before cleaning CAUTION You must keep c o n t r o l a r ea s b u r n e r an d circulating air passageways of h eat er c lean In sp ect t h ese ar eas of heater before each u se H ave h eat er insp ec t ed yearly by a qualified service person H e...

Страница 11: ... Some burner flame holes may become blocked by debris or rust with no flame present If so turn off heater and let cool Either remove blockage or replace burner Blocked burner flame holes will create soot TROUBLE SHOOTING Note All troubleshooting items are listed in order of operation WARNING Turn off heater and let cool before servicing Only a qualified service person should service and repair hea...

Страница 12: ... connected 1 C l e a n b u r n e r s e e C l e a n i n g and Maintenance page 10 or replace burner orifice 2 Contact local propane LP gas company 3 Replace burner orifice 4 Reconnect leads Delayed ignition burner 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact local gas company 2 Clean burner see Cleaning and Maintenance page 10 Burner backfiring during combustion 1 Damaged bu...

Страница 13: ... W C 3 W C Inlet Gas Pressure In of water Maximum 14 10 5 Minimum 11 5 Dimensions Inches H W D Stove 38 3 8 26 3 8 14 1 8 Carton 37 29 5 16 15 5 16 Weight lbs Stove 73 73 Shipping 89 89 For purposes of input adjustment GFP2506 GFN2505 carton dimension 41 3 8 29 5 16 17 3 8 FMK2502 FMK2504 GFP2506 FMK2501 FMK2503 GFN2505 ...

Страница 14: ... Purchase date l warranty card Usually we will ask you to return the defective part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they can not supply original re placement part s call World Marketing s number on the front page REPLACEMENT PARTS ACCESSORIES Purchase these heater accessories from your local dealer or call KOZY WORLD s Sales Department at 814 6...

Страница 15: ...1 5 ILLUSTRATED PARTS BREAKDOWN FMK2501 FMK2502 FMK2503 FMK2504 GFN2505 GFP2506 ...

Страница 16: ...E3 Burner LP 1 1 07 EL024 01 Injector NG 1 1 08 EL025 01 Injector LP 1 1 09 EB37000 Outlet Tube Assembly 1 1 10 EB37001 Outlet Tube Assembly 1 1 11 NRV81F1 3 Regulator RV81FI3 NG 1 1 12 NRV81F1 8 Regulator RV81FI8 LP 1 1 13 EB36000 Inlet Tube Assembly 1 1 14 EB36001 Inlet Tube Assembly 1 1 15 EB38000 ODS Inlet Tube Assembly 1 1 16 EB38001 ODS Inlet Tube Assembly 1 1 17 SIT545 218 SIT Thermostat Co...

Страница 17: ...1 7 ILLUSTRATED PARTS BREAKDOWN FMK2501 FMK2502 FMK2503 FMK2504 ...

Страница 18: ...ket 1 1 7 EL010 01C Upper Decorating Frame 1 1 8 EL011 01 Upper Decorating Wire 1 1 9 EL002 03 01 Upper Mid Louver 1 1 10 EL005 01 Side Reflector 1 1 11 EL007 01 Firebox Floor 1 1 12 EL012 01 Lower Front Panel 1 1 13 EL013 01 Door 1 1 14 224 Brass Knob 1 1 15 EL018 01 Pedestal 1 1 16 EL021 01 Rome Column 2 2 17 EL021 01A Rome Column Decorating Assembly 1 1 18 EL039 01 Leg 1 1 19 EB008 01 Screen 1 ...

Страница 19: ...1 9 ILLUSTRATED PARTS BREAKDOWN GFN2505 GFP2506 ...

Страница 20: ...de Panel 1 1 9 EL015 06 C Left Right Side Panel 1 1 10 EL015 06 DO Left Right Side Panel 1 1 11 EL019 01 Back Panel 1 1 1 12 EL004 06 Regulator Bracket 1 1 1 13 EL010 01C Upper Decorating Frame 1 1 1 14 EL011 01 Upper Decorating Wire 1 1 1 15 EL002 03 01A Upper Mid Louver 1 1 1 1 1 1 16 EL006 06 Side Reflector 1 1 1 17 EL007 06 Firebox Floor 1 1 1 18 EL012 06A 06B Lower Front Panel 1 1 1 1 1 1 19 ...

Страница 21: ...g logs l Fasten decorating logs 1 2 3 onto the correspondent angle iron Figure 4 l Insert the pinhole on the upper part of log 4 into the pin on the left side of log 1 Place the lower part on the flat roof at the left side of log 3 Figure 5 l Insert the pinhole on the upper side of log 5 into the pin on the right side of log 1 Place the lower part on the flat roof at the right side of log 3 Figure...

Страница 22: ...A GFN2505 GFP2506 model Guide the operating control hous ing through the bottom hole of rear panel and place it on the mount ing bracket in the door Mounting operating control housing to the mounting bracket with two screw see figure 4 B GFN2505 GFP2506 model Insert operation control housing at the back bottom of stove Use two black screws provided in blower kit Mount blower operation control hous...

Страница 23: ...Routing Power Cord Figure 3 B Routing Power Cord Figure 5 Mounting Control Housing WiringDiagram Decal INSTALLING BLOWER ACCESSORY BLOWER ACCESSORY MODEL NFHTX186 MODEL GFN2505 GFP2506 Figure 4 Mounting Control hosing ...

Отзывы: