56
Platinum Bio
controller service manual - ENGV 04.11
Experts in heating
5. Main menu
1
8.5
S
o
l
ars
1
8.5.
1 St
a
t
us
1
8.5.2
S
e
tt
ings
Description of the functions
in the SETTINGS submenu
1
8.5.
3 S
ervice
Description of the functions
in the SERVICE submenu
FUNCTION
DESCRIPTION
Activation Delta
The temperature diff erence
between the collector and the
heated water needed to start
up the solar pump.
Deactivation Delta
The temperature diff erence
between the collector and
the heated water needed to
deactivate the solar pump
FUNCTION
DESCRIPTION
Schemat
Determines the solar
system type.
Flow [l/min]
Flow of the factor via the solar
system during the pump
operation. The parameter
needed to calculate the power
oof the collectors.
Fluid heat
Specifi c heat of applied solar
fl uid given in kJ / (kg * ° C)
Water max. temp.
Max. temperature
of heated water.
MAX T. collector alarm
Maximum temperature of the
collectors above which
the protective procedure is
triggered and the alarm is
generated
MIN T. collector alarm
Minimum temperature of the
collectors below which the
protective procedure is
triggered and the alarm is
generated.
Solar pump test
Starts the solar pump
independently of other settings
5.5
S
olars
5.5.
3
S
ervice
5.5.1
S
tatus
5.5.2
S
etting