Service / Configuration
Service / Configuration
SERVICE / CONFIGURATION:
Configuration
Adaptation of the heat pump:
* Changes in the configuration menu are possible after entering an access code. When prompted
for an access code, turn the navigation dial to the required code and confirm the code by pressing
the dial. If you want to retract from the code request screen, hold the navigation dial or wait until
automatic return to main function screen.
Code: 987
•
Central heatinge:
- Regulation:
Per curve - temperature in CH installation is calculated on the basis of outside
temperature and room temperature based on scheduleu,
Constant - in CH installation is equivalent to Supply temperature MAN, set individual
for CH1 and CH2.
- Glycol exchanger:
Yes - there is an additional exchanger in the system
No - there is no addeitional exchanger.
- Building protection:
Yes - if the temperature in the building drops below 7C in the stand-by mode and
the outside temperature is lower than 2C, heating will be turned on ,
No - protection is disabled..
- Time of turning on the immersion heater: this parameter defines the time after
which the heat pump is assisted it will be additional source of heat if it does not
reach the set values parameters. The time is counted from the moment the point
temperature is reached bivalent
[Configuration -> Heat pump -> Bivalent point]
. In
case of if the outside temperature is above the bivalent point temperature, the
additional heat source will not be turned on. In case of need for an additional heat
source, the condition for its activation is the activation of the immersion heaters
[Configuration -> Heating element -> use of immersion heaters: Yes]
,
- Outside temp. Off: setting of selected temperature above which CH circuit will be
switched off.