Drainage pipe installation
Indoor
unit
More than 50mm
More than 25mm
Plug
Water storage pipe
6.2.7 Lifting pipe setting of indoor unit with water pump
The length of lifting pipe should not exceed the pump head of indoor unit water pump.
Pump head of big four way cassette: 750mm
Pump head of compact four way cassette: 500mm
The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong
operation of water level switch.
Refer the following picture for installation reference.
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipe
≤
150mm
B: Lift height
≤
the pump head of water pump
Down incline pipe
B
6.2.8 Bl
ow
hole setting
For the concentrated drainage pipe system, there should
be a
design
ed
blowhole at the highest point of main
pipe to ensure the condensate water discharge smoothly.
The air outlet shall face down to prevent dirt entering pipe.
Each indoor unit of the system should be installed it.
The installation should be considering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
6.2.9 The end of drainage pipe shall not contact with ground directly.
96
Содержание KV 24CC-ARF21
Страница 1: ......
Страница 5: ...3...
Страница 13: ...Dimensions 2 Dimensions Unit mm MODEL A B C H KV24CC ARF21 230 15 9 9 52 260 11...
Страница 14: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12...
Страница 15: ...Wiring Diagrams 4 Wiring Diagrams KV24CC ARF21 13...
Страница 21: ...Field Wiring 11 Field Wiring KV24CC ARF21 19...
Страница 27: ...Dimensions 2 Dimensions Capacity Btu h A H 36 245 275 48 245 275 25...
Страница 28: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 26...
Страница 29: ...Wiring Diagrams 4 Wiring Diagrams KV36CC ARF21B KV48CC ARF21B 27...
Страница 34: ...Field Wiring 9 Field Wiring KV36CC ARF21B KV48CC ARF21B 32...
Страница 36: ...34...
Страница 38: ...Service Space 3 Service Space 36...
Страница 39: ...Wiring Diagrams 4 Wiring Diagrams KV24CM ARF21 37...
Страница 42: ...Air Velocity and Temperature Distributions Reference Data Discharge angle 60 FLOOR Airflow velocity 40...
Страница 46: ...Field Wiring 11 Field Wiring KV24CM ARF21 44...
Страница 48: ...46...
Страница 50: ...Service Space 3 Service Space 48...
Страница 51: ...Wiring Diagrams 4 Wiring Diagrams KV36CM ARF21B KV48CM ARF21B 49...
Страница 54: ...Field Wiring 9 Field Wiring KV36CM ARF21B KV48CM ARF21B 52...
Страница 56: ...54...
Страница 57: ...Dimensions 2 Dimensions Dimension Mode W mm D mm H mm KV36FM ARF21 550 350 1800 KV60FM ARF21 610 390 1925 55...
Страница 58: ...Service Space 56 GA Floor standing Type 3 Service Space 56...
Страница 59: ...Wiring Diagrams 4 W iring Diagrams KV36FM ARF21 KV60FM ARF21 57...
Страница 61: ...Sound Levels 6 Sound Levels Model Noise level dB A H L KV36FM ARF21 56 51 KV60FM ARF21 57 51 59...
Страница 62: ...Accessories 7 Accessories 60...
Страница 64: ...Field Wiring 9 Field Wiring KV36FM ARF21 KV60FM ARF21 62...
Страница 70: ...Wiring Diagrams 4 Wiring Diagrams KV24ODU ARF21 220075301510 KV24ODU ARF21 220075301740 68...
Страница 71: ...Wiring Diagrams KV36ODU ARF21 B 220075501730 KV36ODU ARF21 B 220075502120 69...
Страница 72: ...Wiring Diagrams KV48ODU ARF21B 70...
Страница 73: ...Wiring Diagrams KV60ODU CRF21 71...
Страница 113: ...Troubleshooting 2 1 5 Display board of Floor standing 111...
Страница 118: ...2 4 1 2 Outdoor unit malfunction 116...
Страница 121: ...Troubleshooting Electrical Control System 2 4 2 2 E2 malfunction 119...
Страница 122: ...2 4 2 3 E3 malfunction 120...
Страница 126: ...2 4 2 7 P1 malfunction Only for 36K 52K 124...
Страница 127: ...Troubleshooting 2 4 2 8 P2 malfunction Only for 36K 52K 125...
Страница 128: ...2 4 2 9 P3 malfunction 126...
Страница 131: ...Troubleshooting 2 4 2 12 P6 malfunction For single phase units 129...
Страница 133: ...Troubleshooting 2 4 2 14 P7 malfunction 131...